6-10KVA Rack-mount UPS User Manual Operation
23
This UPS system has parallel machine function, if you want to add single machine to
parallel system, please follow operational process of joining new machine; if you must
remove UPS, please follow operational processes of removing parallel machine.
2. How to install a new parallel UPS system:
1) Before installing a new parallel UPS system, user need to prepare the input and
output wires, the output breaker, and the parallel cables.
2) Open the input and output breakers of each UPS. Connect the input wires, output
wires and battery wires.
3) Connect each UPS one by one with the parallel cables.
4) Close the battery breakers and the input breakers of all of the UPSs in the parallel
system in turn.
5) Turn on each UPS in turn and observe their display. Make sure that each UPS
displays normal and all the UPSs transfer to the INV mode normally.
3. How to remove a single UPS from the parallel system:
1) If you need to remove one UPS of the UPSs parallel system which is on normal
running, press the ON/OFF button of the UPS that is confirmed to be removed
continuously and the UPS will cut off its output immediately.
2) Turn the input breaker off, the external mains input breaker, the output breaker and
the battery breaker.
3) Press the others UPSs’s ON/OFF button. All of them transfer to the Bypass mode.
4) Remove the parallel cables of the UPS that need to be removed.
5) Press ON/OFF button of remained UPSs, then press YES to make the UPSs transfer
to INV output.
7.3 Maintenance Bypass
Maintenance Bypass Mode is used when maintenance or replacement is required. The static
transfer switch will perform a transfer of the load from the inverter to the maintenance bypass
source, with no interruption in power to the critical AC load.
NOTE: When the UPS occurs faulty and cannot work in normal, the user could contact with the
nearest office or customer service center, or the head quarter of the company, do not attempt to
repair the UPS by the user, otherwise may cause dangerous and breakdown the UPS.
1. Place the UPS in maintenance bypass mode from inverter mode
:
When the UPS is in inverter mode, please place the UPS on internal bypass
,
make sure that
the inverter is synchronous with it, so as not to risk a short interruption in powering the load.
●
Press “ON/OFF” key, choose ‘’off’’ to turn off the inverter, the inverter status indicator go
off, the buzzer alarms. The load will be transferred to internal bypass. Press
could mute