6-10KVA Rack-mount UPS User Manual                                       Operation 

24 

the alarm, but the alarm message is still indicating on the LCD display to exist until the warning 
eliminate. 

 Move the manual bypass breaker on the rear of the UPS to the bypass position. This 

requires loosening the captive screw and sliding the bracket up and away from the manual 
bypass breaker. The loading supply will be provided by the maintenance bypass. 

 Turn the input circuit breaker off. Please operate it very carefully. Make sure the manual 

bypass breaker is still on until all the operation ends. 

 Turn the battery circuit break of the external battery cabinet off and remove the battery 

connection cable for the long backup model.   

 Loosen the screws between the box and UPS, Then remove the power distribution box 

from the UPS and set it aside, the long backup UPS will shut down at once. For the standard 
UPS,

 

Turn off the UPS in battery mode. 

  There is no display on LCD, only the input and output terminals in the power distribution 

box attached

 

under power, please operate it very carefully when dismount the UPS. 

NOTE: If it is required to maintain the UPS, after remove the power distribution box and battery 

connection cable, please wait about 10 minutes in order that the BUS capacitor voltage in the 

internal automatically discharges. 

2.  Place the UPS in inverter mode from maintenance bypass mode

 

When finish maintenance of the UPS, please use the following steps to switch the load 

supplying from maintenance bypass to inverter. 

NOTE:

 

because it does not have the maintenance circuit breaker secondary contact to insert 

the message into the UPS, the recovering operation of the UPS must strictly follow the 

operation procedure, otherwise may cause the damage of the system.

 

 Align connectors and press box onto UPS. Hold box firmly against UPS. Tighten the 

screws between the box and UPS. 

 Insert the battery connection cable to the right position of the UPS. Turn the battery 

circuit breaker of the battery cabinet on. 

 Turn the input circuit breaker of the distribution box on. 

 When UPS is working in bypass mode, Turn the manual bypass breaker off. Tighten the 

bracket over the manual bypass breaker with captive screws. 

 Press “ON/OFF”, choose ‘’on’’ to open the inverter, UPS switch to the inverter mode. 

NOTE: before you start the inverter, you must be sure that you have turned the manual bypass 

breaker off, otherwise may cause dangerous and breakdown the UPS. 

Summary of Contents for 6KS

Page 1: ...d 220 230 240VAC 50 or 60Hz supply The factory default setting is 220VAC 50Hz Installation instructions and warning notices are in this manual The ups 06 10KVA 220 230 240VAC is designed for use with...

Page 2: ...urn off and unplug the ups before cleaning it z Clean the UPS with a dry cloth Do not use liquid or aerosol cleaners z Never block or insert any objects into the ventilation holes or other openings of...

Page 3: ...6 Battery 7 3 7 Dynamic Bypass 7 4 PRODUCT SPECIFICATION And PERFORMANCE 8 4 1 Model Description 8 4 2 Product Specification and Performance 8 5 INSTALLATION 10 5 1 Unpacking and Inspection 10 5 2 Ra...

Page 4: ...EMENT PROCEDURES 26 9 1 Battery Disposal 26 9 2 External Battery Replacement Procedures 26 9 3 Internal Battery Pack Replacement Procedures 27 10 TROUBIE SHOOTING 28 10 1 Checking UPS status 28 10 2 A...

Page 5: ...corrosive substance This UPS contains no user serviceable parts except the internal battery pack The UPS on off push buttons do not electrically isolate internal parts Under no circumstance attempt t...

Page 6: ...en damage equipment The series protects equipment from these disturbances The series is a compact rack mount on line UPS An on line UPS continuously conditions and regulates its output voltage whether...

Page 7: ...6 10KVA Rack mount UPS User Manual Introduction 3 Fig 2 Front View of standard Model Fig 3 Rear View of 6KVA Long Backup Model Fig 4 Rear View of 10KVA Long Backup Model...

Page 8: ...port SNMP card for network monitoring Intelligent card or non pluggable dry contact card for user extending Input circuit breaker Maintenance Bypass breaker External battery connector Parallel kit op...

Page 9: ...KVA Rack mount UPS User Manual Introduction 5 Fig 6 The Removable Power Distribution Box factory attached of long backup model Fig 7 The Removable Power Distribution Box factory attached of standard m...

Page 10: ...nsuring that the waveform of the input current used by the UPS is near ideal Extracting this sine wave input current achieves two objects z The utility power is used as efficiency as possible by the U...

Page 11: ...ude value regulated non spoilable lead acid batteries outside To maintain battery design life operate the UPS in an ambient temperature of 15 25 C 3 7 Dynamic Bypass The ups provide an alternate path...

Page 12: ...0 60 Input Voltage 176 275 VAC Current 34A max 57A max Battery Voltage 192VDC Current 37A max 60A max Output Voltage 220V 230V 240V Current 27 26 25A 45 43 42A Dimension W H D mm 438 130 680 438 218 6...

Page 13: ...de is above than 1000m the output power must be derated in use please refer to the following Altitude M 1000 1500 2000 2500 3000 3500 4000 4500 5000 Derating Power 100 95 91 86 82 78 74 70 67 1 0 9 la...

Page 14: ...the long backup model 2 Inspect the appearance of the UPS to see if there is any damage during transportation Do not turn on the unit and notify the carrier and dealer immediately if there is any dama...

Page 15: ...into the rack rails NOTE Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the lowest possible rack position 5 2 Connect Input Output Power Cables 1 Notes for inst...

Page 16: ...tached please refer to the appearance diagram 2 For 6KVA UPS it is recommended to select the UL1015 10AWG 6mm 2 wire or other insulated wire which complies with AWG Standard for the UPS input and outp...

Page 17: ...6 10KVA Rack mount UPS User Manual Installation 13 Fig 8 Input and Output Terminal Block Wiring Diagram of distribution box for standard model...

Page 18: ...reen wire or green wire with yellow ribbon wire is used 6 After having completed the installation make sure the wiring connection is correct 7 Please install the output breaker between the output term...

Page 19: ...on 1 The nominal DC voltage of external battery pack is 192VDC Each battery pack consists of 16 pieces of 12V maintenance free batteries in series To achieve longer backup time it is possible to conne...

Page 20: ...tput power sharing and power redundancy 2 Parallel installation 1 Users need to opt two standard 15 pin communication cables which length is appropriate to be less than 3m 2 Strictly follow the stand...

Page 21: ...eaker Fig 11 Wiring Diagram of 6KVA and 10KVA in parallel 3 Operation 1 To perform the general operation follow the stand alone operating requirement 2 Startup The units transfer to INV mode simultane...

Page 22: ...mode It is easy to operate the equipment with no previous training You just need to read through this manual and operate according to the instructions in it Rectifier PFC Inverter Bypass Charger UPS...

Page 23: ...NOTE Not available when UPS is set in automatically start mode 2 Press on off directly when there is no main input press again to start UPS 3 Press on off to shutdown inverter when UPS is in normal mo...

Page 24: ...k inverter is not working BYP Bypass indicator green bypass is normal dark UPS is in normal mode and bypass is normal red bypass fault red flicker bypass alarm BAT Battery indicator green battery char...

Page 25: ...and function Set language contrast communication set SNT Modbus Modbus set Function function 1 transfer to bypass escape fault clear mute on off function 2 battery test maintenance test stop test Hist...

Page 26: ...er of the battery pack is in the ON position this step only for long backup time model 2 Press the ON OFF button once to power on the LCD then press ON OFF button again choose YES to enter 3 A few sec...

Page 27: ...off its output immediately 2 Turn the input breaker off the external mains input breaker the output breaker and the battery breaker 3 Press the others UPSs s ON OFF button All of them transfer to the...

Page 28: ...n the UPS after remove the power distribution box and battery connection cable please wait about 10 minutes in order that the BUS capacitor voltage in the internal automatically discharges 2 Place the...

Page 29: ...ged once every 4 to 6 months if it has not been used for a long time zIn the regions of hot climates the battery should be charged and discharged every 2 months The standard charging time should be at...

Page 30: ...cuit There may be hazardous voltage between the battery terminals and the ground 8 Even though the input breaker is disconnected the components inside the UPS are still connected with the batteries an...

Page 31: ...ery access door from the UPS for reassembly 4 Gently disconnect the battery plugs and battery receptacles 5 Pull the internal battery packs out of the UPS 6 Line up and slide in the new replacement in...

Page 32: ...p and contact your local representative or Channel Support z Check whether the battery is discharging When the utility input is normal the battery should not discharge If the UPS is operating in Batte...

Page 33: ...broken IGBT drivers are lost 17 A1 1 Reserved 18 2 Reserved 19 3 Reserved 20 4 Reserved 21 5 Reserved 22 6 Reserved 23 7 Reserved 24 8 Reserved 25 9 Input voltage Fault OK Fault Input voltage out of r...

Page 34: ...38 6 Negative bus under voltage OK Fault UPS requires service 39 7 Battery reversed OK Fault Check if the battery wires connection is OK 40 8 Reserved 41 9 Reserved 42 10 Reserved 43 11 Reserved 44 1...

Page 35: ...hutdown normal shutdo wn 66 2 INV protect OK Fault 67 3 Transfer times limit in one hour OK Fault Transfer times between inverter and bypass is over 5 times in one hour 68 4 Reserved 69 5 Reserved 70...

Page 36: ...6 Reserved 81 A5 1 Reserved 82 2 Output shorted OK Fault Shutdown UPS and open output breaker check if load is effective or short internally check if output connector is shorted 83 3 Battery test None...

Page 37: ...UPS fail Low voltage if something is failure in UPS If not high voltage 2 General alarm Low voltage if something is abnormal If not high voltage 3 GND 4 Remote shutdown UPS shutdowns rectifier and in...

Page 38: ...dition This function can be activated through a remote contact provided by the user It requires opening NO and 24V at normal operation EPO is activated when shorting NO and 24V Description of Input Po...