For Left Side Connection
Drain Boss
Drain Plug
Rear Side
Fastener Band
Drain Plug
Insulation Plug
Fan Runner
Fan Motor
Remove the drain plug of the left-side drain boss as
indicated in the following procedure.
1. Cut the fastener.
2. Remove the insulation material.
3. Remove the drain plug.
4. Insert the drain plug into the right-side and drain
boss using a driver as shown below.
Driver
Drain Plug
Drain Connection
Unit
Side
5. After inserting the drain plug into the right-side drain
boss, seal the jointed part by using a water-proof
chloride type sealing material and secure it with a
fastener.
Seal Material
Plug
6. Wrap the insulation material around the drain
connection.
7. Connect the drain hose to the left side drain
connection using the same procedure as for the right
side drain connection.
Connecting a Drain Piping
1.
Prepare
a
polyvinyl
chloride
(PVC)
tube
with
an
outer diameter of 26mm. (VP20)
2. Pay attention to the position of the drain pipe. Keep
the down-slope, 1/25 to 1/100. Do not create an upper
slope or rise for the drain piping.
3. Seal the connecting part of the drain pipe by using
the water-proof chloride type sealing material.
4. Wrap the insulation material around the connecting
part perfectly.
5. Fasten the drain pipe to the connecting part using
the factory-supplied clamp.