38
l
Can
BREEZE
Operating and Maintenance Cooling Unit Instructions 8-14 kW
www.canovate.com
l
info@canovate.com
l
P. +90 216 484 2222
entering into the unit. Seal the holes where pipes
and wires are inserted, by using a insulation (
fi
eld-
supplied).
3
If the
fi
eld-supplied piping is connected with
stop valves di- rectly, it is recommended use a tube
bender.
4
Check to ensure that the stop valves are closed
completely before connecting pipes.
5
Connect the
fi
eld supplied refrigerant pipes to
the indoor unit and outdoor unit. Apply the oil thinly at
the seat
fl
are nut and pipe before tightening.
The required tightening torque is as follows:
Pipe Size
Tightening Torque (Nm)
Ø 6.35 mm (1/4)
20
Ø 9.53 mm (3/8)
40
Ø 12.70 mm (1/2)
60
Ø 15.88 mm (5/8)
80
Ø 19.05 mm (3/4)
100
6
After connecting the refrigerant piping, seal the
open space between knockout hole and refrigerant
pipes by using insula- tion material
Unit
Side
Nº
Description
1
Insulation Material
2
Insulation Material
3
Field Supplied
4
Insulation Material
7
Operation of stop valve should be performed
according to the
fi
gure below.
Close before shipment
Outdoor unit stop valve
Spindle Type
8-14 kW
1
2
3
4