MAP2 

Page 3 of 32 

 

Installation Manual 

September 2020 • Rev. 1.5 

Introduction 

Cansec Systems’ MAP2 (Modular Access Panel) incorporates a mini-computer 
called the Panel Logic Module (PLM) utilizing Ethernet connectivity and an Input 
Output Module (IOM) which incorporates a 32-bit processor in this new 
architecture. This allows for a fast, high capacity access control system with a lower 
cost per reader/door system implementation. The MAP2 architecture has the ability 
to flash applications and firmware updates into the control panel using the 
Ethernet connection.  
 
The standard MAP2 is provisioned with the default 2-door configuration. There are 
two modes, 

First Access

 (

application based

) and 

CloudACS 

(cloud based)

. Door 

configuration and mode can be upgraded. However, only one mode can be run at a 
time and data cannot be shared between modes.  The availability of the general-
purpose Input and Output points depends on the number of doors provisioned for 
the controller. The MAP2 controller also supports elevator configurations. 
 
The MAP2 allows for 100,000 individual cardholders, using raw Wiegand data up 
to 64 bits per card ID. This allows the use of many proprietary Wiegand cards 
without the need for data conversion. The readers can be Cansec’s CanProx One 
Proximity Readers (AWID or HID card technology) or one of many other popular 
Wiegand readers. 

 

Note:

 Must have l

atest approved PLM and IOM firmware version for compatibility to this document

 

 

 

 

255 Access Schedules 

 

On board Triggers independent of host connection   

 

Supports 100,000 individual user card IDs 

 

Supports any Wiegand card (64 bit max.)  

 

Supports up to 8 readers/door combinations 

 

Supports Door Contact and RTE connection per reader/door 

 

Supports general-purpose Input points (with or without supervision) and 
Output points 

 

Supports elevator configuration 

 

Ease of future software/firmware upgrades 

 

First Access mode or CloudACS mode 

 

Key Features 

 

 

Summary of Contents for MAP2

Page 1: ...MAP2 Controller INSTALLATION MANUAL September 2020...

Page 2: ...Contact Wiring 12 Lock Output and Multi Function Relay Wiring 15 Input and Output Point Wiring 17 Appendix 20 MAP2 System Indicators 21 Power Connector 22 SHDN Shutdown Button 23 IP Address Reset and...

Page 3: ...ty of the general purpose Input and Output points depends on the number of doors provisioned for the controller The MAP2 controller also supports elevator configurations The MAP2 allows for 100 000 in...

Page 4: ...ity readers with 100 mA each 12VDC 1 5A Temperature Range Operating 0 C to 60 C Storage without lithium battery 40 C to 105 C Relative Humidity Operating 20 to 80 Auto Resettable Fuses MAP2 Main 12V D...

Page 5: ...ax Length NOTE Consult reader specifications as 12 gauge wire may be required for power Dimensions Weight MAP2 Controller 7 L x 7 W 18 cm L x 18 cm W MAP2 Enclosure 13 W x 19 H x 3 5 8 D 33 cm W x 48...

Page 6: ...lines creating misreads This Wiegand misread issue is more evident on longer Wiegand reader cables The reader cable may have to be replaced with the correct type of Wiegand reader cable to improve sys...

Page 7: ...MAP2 Page 7 of 32 Installation Manual September 2020 Rev 1 5 MAP2 Controller Layout Figure 1...

Page 8: ...output points c 6 door configuration 6 lock relays 6 multi function relays 6 REX RET 6 door contacts DPS 2 general purpose input points and 2 general purpose output points d 8 door configuration 8 lo...

Page 9: ...ler is set to acquire an IP address automatically DHCP However it can be optionally set to a static IP address or reset if necessary See Appendix section for more information Mechanical Information 1...

Page 10: ...ontroller and a separate power supply which can be sized to supply the amount of current that the attached high current devices locks will require Figure 5 Mode Indicator After a complete power up the...

Page 11: ...1 of 32 Installation Manual September 2020 Rev 1 5 ENTRY READER WIRING The following diagram shows entry reader wiring only For entry and optional exit reader wiring diagram proceed to the next sectio...

Page 12: ...4 uses Input 7 Door Contact DPS and Input 8 RTE REX Reader 5 uses Input 9 Door Contact DPS and Input 10 RTE REX Reader 6 uses Input 11 Door Contact DPS and Input 12 RTE REX Reader 7 uses Input 13 Door...

Page 13: ...MAP2 Page 13 of 32 Installation Manual September 2020 Rev 1 5 Figure 8 Non Supervised The RTE REX can be set to Normally Open or Normally Closed from the host software...

Page 14: ...MAP2 Page 14 of 32 Installation Manual September 2020 Rev 1 5 Figure 9 Supervised The RTE REX can be set to Normally Open or Normally Closed from the host software...

Page 15: ...one of the following options Alarm Shunt factory default Shunt the alarm system before opening lock Door Held Open Door has been left open Forced Entry Door opened without access granted or exit butt...

Page 16: ...sdiction to verify the specific requirements Also a building permit may be required in some jurisdictions for the installation of magnetic locks Figure 11 See Note 2 in Appendix section for 6 Amp rela...

Page 17: ...Manual September 2020 Rev 1 5 INPUT AND OUTPUT POINT WIRING General Layout The MAP2 can be provisioned for all I O which allows for 16 input points and 16 output points to be used There is no door pro...

Page 18: ...uire a Cansec CA EOL resistor pack to be placed at the device being monitored Supervised input points will inform the host of 4 supervised states Alarm Secure Trouble High and Trouble Low These are th...

Page 19: ...MAP2 Page 19 of 32 Installation Manual September 2020 Rev 1 5 Output Wiring Figure 14...

Page 20: ...AH batteries 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 55mm 6 65 lbs 3 02 kg 12 24 VDC selectable output 6 Amp Enclosure Style Power Supply with Backup Battery Charger Eight individual Class 2 rated pow...

Page 21: ...NDICATORS 12VDC POWER LED ON indicates 12 volts DC is connected First Access Mode Mode indicator MAP2 emits 1 beep after powered up CloudACS Mode Mode indicator MAP2 emits 3 beeps after powered up BD...

Page 22: ...CTOR Connections TAMPER allows for the connection of an Enclosure Tamper Switch Figure 15 Factory default The Tamper jumper is set to disabled To activate the Panel Tamper move jumper to the top 2 pin...

Page 23: ...not occur try the procedure again If it still does not respond correctly as described above a system fault has occurred It will be necessary to unplug the power connector and re insert it after 10 se...

Page 24: ...ng green along with a short series of beeps 1 or 3 beeps to indicate its respective provisioned mode First Access or CloudACS 4 Plug the MAP2 to the network with a DHCP server available 5 Install and...

Page 25: ...Host IP see Figure 21 instructs the panel to accept data connection only from the host computer where the First Access software is installed Other connections for diagnosis and updating are not limite...

Page 26: ...ON TOOL 1 If the MAP2 controller is already powered off then proceed to step 3 Otherwise press and hold the SHDN button until the STAT LED on the module begins flashing rapidly then release the shutdo...

Page 27: ...l emit a series of beeps 1 beep or 3 beeps to indicate its provisioned mode First Access or CloudACS respectively 5 Remove the USB flash drive from the MAP2 controller 6 Insert the flash drive into a...

Page 28: ...omputer is connected to SrvPort 5000 Factory default server port You may change it or leave it as default DiagPort 5001 Factory default diagnostic port You may change it or leave it as default UpdateP...

Page 29: ...ly Remove the line USB INIT DONE and save the file before removing it from your computer 9 Repeat from step 1 to step 6 then proceed to step 10 10 Insert the flash drive into a USB port on a computer...

Page 30: ...it button event A message will be transmitted to the host software if the panel is online DOOR HELD OPEN OUTPUT The MF multifunction relay when configured as Door Held Open will be activated if the lo...

Page 31: ...ARDS ONLY The MF multifunction relay when configured as Door Operator_HC will only be activated by cards designated as handicap and by exit button press The lock relay will be activated first followed...

Page 32: ...MAP2 Page 32 of 32 Installation Manual September 2020 Rev 1 5...