CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Note:
1. The priority of frequency source is Fire mode >JOG >Frequency bind >Force to
PID >Force to PLC >Force to digit set >Multi speed >Configuration of main and
auxiliary frequency source parameter configuration.
2. The enforcement action of frequency source through the terminal, equals to modify
b2.00(Main frequency source option A) as corresponding value. For example,b2.00
= 0(Main frequency source option A), it
’s equal to modify b2.00 = 5(PID) when a X
terminal with the configuration of function 56 is effective.
Table 6- 5 Multi-reference configuration choice
Multi-reference
terminal 4
Multi-reference
terminal 3
Multi-reference
terminal 2
Multi-reference
terminal 1
Setting frequency
OFF
OFF
OFF
OFF
Multi-reference 0
(
E2.01
)
OFF
OFF
OFF
ON
Multi-reference 1
(
E2.02
)
OFF
OFF
ON
OFF
Multi-reference 2
(
E2.03
)
OFF
OFF
ON
ON
Multi-reference 3
(
E2.04
)
OFF
ON
OFF
OFF
Multi-reference 4
(
E2.05
)
OFF
ON
OFF
ON
Multi-reference 5
(
E2.06
)
OFF
ON
ON
OFF
Multi-reference 6
(
E2.07
)
OFF
ON
ON
ON
Multi-reference 7
(
E2.08
)
ON
OFF
OFF
OFF
Multi-reference 8
(
E2.09
)
ON
OFF
OFF
ON
Multi-reference 9
(
E2.10
)
ON
OFF
ON
OFF
Multi-reference 10
(
E2.11
)
ON
OFF
ON
ON
Multi-reference 11
(
E2.12
)
ON
ON
OFF
OFF
Multi-reference 12
(
E2.13
)
ON
ON
OFF
ON
Multi-reference 13
(
E2.14
)
ON
ON
ON
OFF
Multi-reference 14
(
E2.15
)
ON
ON
ON
ON
Multi-reference 15
(
E2.16
)
C0.02
①
Range: 0~58
Default: 23
X2 function
Same as
C0.01
.
C0.03
①
Range: 0~58
Default: 0
X3 function
Same as
C0.01
.
C0.04
①
Range: 0~58
Default: 0
X4 function
Same as
C0.01
.
C0.05
①
Range: 0~58
Default: 0
X5 function
Same as
C0.01
.