CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Example 1:
Two lines 1.
Terminal X1 controls forward run, and X2 controls reverse run. The parameters’
configuration show as following table.
Table 6- 6
Two lines 1 parameters’ configuration
Parameter
Setting
C0.17
(Terminal command mode)
0
(
Two lines 1
)
C0.01
(
X1 terminal function
)
3
(
Run forward
)
C0.02
(
X2 terminal function
)
4
(
Run reverse
)
The wiring is shown in the following figure. Among them:
When K1 closed, the AC drive run forward:
When K2 closed, the AC drive run reverse:
When K1 and K2 have the same status, the AC drive stopped:
Both X1,X2 are level active.
K2
K1
Run command
0
0
Stop
1
1
Stop
0
1
Run forward
1
0
Run reverse
Figure 6- 9 Two lines 1
Example 2:
Two lines 2.
Terminal X1 controls run and stop,
terminal X2 controls run direction. The parameters’
configuration show as following table.
Table 6- 7
Two lines 2 parameters’ configuration
Parameter
Setting
C0.17
(
Terminal command mode
)
1
(
Two lines 2
)
C0.01
(
X1 terminal function
)
3
(
Run forward
)
C0.02
(
X2 terminal function
)
4
(
Run reverse
)
Although the configuration of C0.01 and C0.02 are the same, but they have
different meaning between two line type 2 and two line type 1.