CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Eb.28
Range: 0.00~
b0.00
Default: 2.00
Simple brake
frequency
Unit: Hz
In the process of stopping,Y/T terminal assigned with function
‘45: Simple
brake control
’ will be ON for the time
Eb.29
set when the AC drive output
frequency is lower than
Eb.28
.
Eb.29
Range: 0.0~3000.0
Default: 0.0
Simple brake
time
Unit: Sec
Set
Eb.29
to a nonzero value will enable simple brake function.
Group F0: Protection
F0.00
Range: Model dependent
Default: Model dependent
Under voltage
threshold
It is used to set the undervoltage threshold for the drive. The default value
and range of different classes are list in the following table.
Table 6- 17 Undervoltage threshold in different voltage class
Voltage Class(V)
Default(V)
Range(V)
Voltage Class(V)
Default(V)
Range(V)
Single-phase 220
200
180 - 280
Three-phase 480
450
350 - 600
Three-phase 220
200
180 - 280
Three-phase 690
650
500 - 800
Three-phase 380
350
280 - 550
Three-phase 1140
1350
1100 - 1500
F0.01
①
Range: Model dependent
Default: Model dependent
Over voltage
threshold
It is used to set the overvoltage threshold for the drive. The default value
and range of different classes are list in the following table.
Table 6- 18 Overvoltage threshold in different voltage class
Voltage Class(V)
Default(V)
Range(V)
Voltage Class(V)
Default(
V)
Range(V)
Single-phase 220
380
360 - 410
Three-phase 480
880
660 - 900
Three-phase 220
380
360 - 410
Three-phase 690
1200
1100 - 1300
Three-phase 380
780
630 - 800
Three-phase 1140
2400
2300 - 2500
F0.02
Range: 0~1
Default: 1
Input phase loss
protection
0: Disable If input phase loss then drive will not perform protecting action.
1: Enable If input phase loss then drive will perform protecting action
according to F0.19(Unit's digit).
Note:
This protection is valid only in the AC drives which power are larger
or equal than 11KW(G type).
F0.03
Range: 0~1
Default: 1
Output phase
loss protection
0: Disable If out phase loss then drive will not perform protecting action.
1: Enable If input phase loss then drive will perform protecting action
according to F0.19(Ten's digit).