CDE360 Vector Control AC Drive Chapter 6 Parameters Description
-
92
-
A0.53
Range: 0.0~6553.5
Default: 0.0
Running time
Unit: Min
It is used to display the current running time of the drive, the unit is 0.1
minute.
A0.54
Range: 0~9999
Default: 0
Accumulative
power-on day
Unit: Day
It is used to display the accumulative power-on day of the drive since the
delivery. It add
A0.55
is equal to the total accumulative power-on time.
A0.55
Range: 0.00~23.99
Default: 0.00
Accumulative
power-on hour
Unit: h
It is used to display the accumulative power-on hour of the drive since the
delivery. It add
A0.54
is equal to the total accumulative power-on time.
A0.56
Range: 0~9999
Default: 0
Accumulative
running day
Unit: Day
It is used to display the accumulative running day of the drive. It add
A0.57
is equal to the total accumulative running time.
A0.57
Range: 0.00~23.99
Default: 0.00
Accumulative
running hour
Unit: h
It is used to display the accumulative running hour of the drive. It add
A0.56
is equal to the total accumulative running time.
A0.58
Range: 0~65535
Default: 0
Accumulative
power
consumption
Unit: kWh
It is used to display the accumulative power consumption of the drive until
now.
A0.59
Range: 0.0~300.0
Default: 0.0
Motor
temperature
Unit:
℃
The signal of the motor temperature can be sampled by PT100/PT1000
optional card. If the PT100/PT1000 optional card not be inserted, motor
temperature will be display the default value(0.0
℃
).
A0.60
Range: -40.0~125.0
Default: 0.0
Inverter module
temperature
Unit:
℃
It is used to display the IGBT temperature of the inverter module.
A0.61
Range: -40.0~125.0
Default: 0.0
Rectifier module
temperature
Unit:
℃
It is used to display the rectifier bridge temperature.