CDE360 Vector Control AC Drive Chapter 6 Parameters Description
The wiring is shown in the following figure. Among them:
If K1 closed, K2 broken open the AC drive run forward, K2 closed the AC drive
run reverse; If K1 broken open, the AC drive stop running. Both X1 and X2 are level
effective.
K2
K1
Run command
0
0
Stop
1
0
Stop
0
1
Forward
1
1
Reverse
Figure 6- 10 Two lines 2
Example 3:
Three lines 1.
X1 controls forward run, X2 controls reverse run,
X3is run enable. The parameters’
configuration is shown as the table below.
Table 6- 8
Three lines 1 parameters’ configuration
Parameter
Setting value
C0.17
(
Terminal command mode
)
2
(
Three lines 1
)
C0.01
(
X1 terminal function
)
3
(
Forward run
)
C0.02
(
X2 terminal function
)
4
(
Reverse run
)
C0.03
(
X3 terminal function
)
5
(
Three lines run control
)
By the“forward run” terminal controls the AC drive run forward,“reverse run” terminal
controls the AC drive run reverse,
“Three lines run enable”terminal controls the AC drive
stop.
The wiring is shown below in the following figure. Among them:
For normal starting and running, the SB3 button must remain closed;
If the SB3 button is closed, press the SB1 button the AC drive is run forward, press
the SB2 button, the AC drive is run reversed;
At the moment of SB3 broken open, the AC drive shutdown;
X1 and X2 receives invalid command at the moment of rising edge in closing action,
it is pulse trigger effective.