CDE360 Vector Control AC Drive Chapter 6 Parameters Description
H0.12
Range: 0~3
Default: 2
Dead zone
compensation
mode selection
0: No compensation
1: Rectangle compensation
2: Trapezoid compensation
3: Trapezoid at Low frequency and rectangle at high frequency
H0.13
①
Range: 1~2048
Default: 1024
Dead zone
compensation
size
It is used to increase or decrease the dead zone compensation based on
the default dead compensation value.
H0.14
①
Range: 1~3640
Default: Model dependent
Angle size when
current across
zero
It is used to set the angle size when current across zero, the 3640
equivalent to 20 degrees.
H0.15
①
Range: 0.10~300.00
Default: 50.00
Dead zone
compensation
filter cut off
frequency 1
Unit: Hz
To improve the precision of the output voltage, current sample harmonic
needs to be filtered.
The parameter is used to set the filter frequency when drive in different
output frequency.
H0.16
①
Range: 0.10~300.00
Default: 200.00
Dead zone
compensation
filter cut off
frequency 2
Unit: Hz
Please see the following figure.
H0.17
①
Range: 0.10~
H0.18
Default: 5.00
Dead zone
compensation
switchover
frequency 1
Unit: Hz
Please see the following figure.
H0.18
①
Range:
H0.17
~
b0.00
Default: 50.00
Dead zone
compensation
switchover
frequency 2
Unit: Hz
Please see the following figure.