CDE360 Vector Control AC Drive Chapter 5 Parameter List Table
-
63
-
d1 Motor Parameters
Function
Code
Name
Range
Default
Step
Description
d1.01
①
Motor stator
resistance
Module
dependent
Module
dependent
0.001ohm
d1.02
①
Motor rotor
resistance
Module
dependent
Module
dependent
0.001ohm
d1.03
①
Motor leakage
inductance
Module
dependent
Module
dependent
0.01mH
d1.04
①
Motor mutual
inductance
Module
dependent
Module
dependent
0.1mH
d1.05
①
Motor No-load
current
Module
dependent
Module
dependent
0.01A
d1.06
①
Motor weaken flux
coefficient 1
0.000~1.000
0.400
0.001
Flux weakening coefficient at
20% flux current
d1.07
①
Motor weaken flux
coefficient 2
0.000~1.000
0.700
0.001
Flux weakening coefficient at
50% flux current
d1.08
①
Motor weaken flux
coefficient 3
0.000~1.000
1.000
0.001
Flux weakening coefficient at
80% flux current
d1.15
①
Auto tune
0~2
0
1
0: No action
1: Static auto tune
2: rotational auto tune
d2 Speed Control
Function
Code
Name
Range
Default
Step
Description
d2.00
ASR proportional gain Kp1
1~100
20
1
d2.01
ASR integration time Ti1
0.01~10.00
0.30
0.01Sec
d2.02
ASR proportional gain Kp2
1~100
20
1
d2.03
ASR integration time Ti2
0.01~10.00
0.50
0.01Sec
d2.04
Low speed switchover
frequency
0.00~d2.05
5.00
0.01Hz
d2.05
High speed switchover
frequency
d2.04~b0.00
10.00
0.01Hz
d2.06
ASR integration attribute
0~1
0
1
0: Integral separated inactive
1: Integral separated active
d2.07
Vector control slip gain
50~120
100
1%
d2.08
ASR filter time
0~1023
0
1