background image

10 

1>.  De-solder  the  capillary  and  re-solder  in  the  correct  position  avoiding  contact  with  the  inside  of  the 

evaporator, (The depth should be within 15mm), then recharge the unit with refrigerant see 

(

7)

 

2>.  If  the  capillary  touches  the  inside  of  the  cabinet  or  air  duct  board,  you  should  adjust  position  of 

capillary and pack it with anti-vibration compound.

 (Fig.8 & Fig.9

Fig.9.1)

 

 

  Oil jammed noise 

Fault: intermittent and deep jet noise coming from inside of the capillary. 
Caused  by:  Compressor oil  flowing  into  the  cooling  system  pipe  work because of  wine  cooler  lean during 
transportation, and the jetting oil in the capillary cause noise.   

Solutions:

 

Clean the cooling system pipe, and recharge with refrigerant see 

(page 7)

     

 

  Evaporator freezing 

  This is normally due to   

A/ Poor seal between door and door frame 

B/ The door not closed correctly for a long period of time 

This allows  moist air into the cabinet, which  freezes in the evaporator, if the ice is allowed to get too thick, it 

may damage the fan.   

1>. Ensure door is sealed against the frame, if there is slight distortion of the seal, heat the effected area gently 

with  a  hair dryer  genrly see 

(fig 12) 

with smooth strokes of the hair dryer, then when still warm pull the effected 

area  back  into  its  original  position,  this  process  may  have  to  be  repeated  until  the  seal  is  completely  back  to  its 

original condition.

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig.12

 

2>. If the ice has damage the fan it will need to be replaced see. 

(Fig.10)

 

In some older models, the electrical connector of the fan wires is fixed under the evaporator, and water 

from evaporator may drip onto this junction box ,this may effect the electrical connection ,causing the fan 
to stop. Which in turn causes surface freezing.

 

1>.  Remove  the  air  duct  board  see

(Fig.1,  Fig.2  ,Fig.3,Fig.4  &  Fig.5)

,  remove  the  cable  clip  securing 

screws(A), and remove the cable clip see 

(Fig.13)

 

    2>. Cut off the both connectors see. 

(Fig.13.1)

 

3>. Strip the ends of the wires about 12mm and re-connect then

Ensure this electrical joint is sealed against future water damage, and is electrically safe

(Fig.14)

 

Summary of Contents for JLWF302

Page 1: ...JLWF302 Caple Wine Cabinet Caple Wine Cabinet Technical information ...

Page 2: ......

Page 3: ...ator fan 1 16 DG13 158 Surpport pole 1 17 DG22 209 Air duct board 1 18 DG13 198 Senser cover 1 19 DG8 8 Senser 1 20 DG19 1 Fan cover 1 21 DG3 12 W LED lamp plant LED 1 22 DG22 395 Plastic power box 1 23 DG13 327 Surpport 1 24 DG13 1 2 Water tank 1 25 DG15 26 1 Wooden shelves A9A 1 26 DG15 25 Shelves decorate piece 5 27 DG23 227 Door Asm 1 28 DG22 3057 Door axis 1 29 DG15 27 Wooden shelves C1 1 30 ...

Page 4: ...de Description Qty JLWF302 Caple Wine Cabinet 39 DG12 3 Condenser 1 40 DG7 3 2 BH Condenser fan 1 41 DG19 3 Fan cover 1 42 DG14 33 Fan fixing piece 2 43 DG12 58 Circumfluence pipe 1 44 DG22 39 Compressor bracket 1 ...

Page 5: ......

Page 6: ...JLWF302 Caple Single zone wine cabinet Caple Single zone wine cabinet Service Manual ...

Page 7: ...rm the electrical supply to prevent electrical shock Preparation before maintenance Tools 1 Pliers 2 Phillips head screwdrivers 3 Process pipe 4 Electrical Multi meter 5 Amp meter 5A caliper cable type 6 Electrical soldering iron 7 Wire strippers 8 Seal pliers 9 Scissors Equipment 1 Vacuum pump 2 Soldering iron for copper pipes 3 Gas meter Cooling system fault How to Evaluate the fault Page 3 How ...

Page 8: ... Fault finding by the self check mode Page 12 Sensor fault Page 12 LED display fault Page 14 How to remove the electrical box Page 14 The dismantlement method of the electrical box spear part Page 14 How to replace the light Page16 How to replace the Decorative frame Page17 ...

Page 9: ...pe and please put the hand close to the cut kerf of the vent pipe If there is a little gas leak form the terminal it means normal or it is jamed B Make sure the capilary is working normally when the drainpipe is connetced again and infuse 0 8 1MP nitrogen then test the leakage if the cooling system of the soldering point with the soap water Check from the the soldering point arround the compressor...

Page 10: ...an ambient temperature of 32 and the unit is empty How to remove the air duct board 1 Remove the shelves firstly a Remove the shelves some models have Phillips head screws to hold other models have no screws Fig 1 Fig 1 Pull the shelves to the bottom circumvolve any side of the right and left and let the setter of the shelve go out of the channel and then draw out the shelves Fig 2 Fig 2 ...

Page 11: ...in different types the situations and quantity of them are different A D are the screws fixing the fan no need to remove Remove the fixing screws of air duct board 1 2 3 4 5 6 7 8 9 10 then pull out air duct board A See Fig 5 Be attention to unplug the connection wire when removing the air duct board You can move slowly aside until you can see the fans wire and unplug it and then take out the whol...

Page 12: ...r duct board see Fig 6 Fig 7 Diagram showing the front side soldered joints There are two different types of evaporator Finned and pipe evaporator se Fig 6 Fig 7 A Capillary soldered joints B evaporator soldered joints Fig 6 Finned evaporator Fig 7 Pipe board evaporator ...

Page 13: ...denser See Fig 9 Fig 9 1 B Dry filter process pipe soldered joint C Dry filter soldered joint D Capillary soldered joint E Process pipe soldered joint F Suction pipe soldered joint G Discharge pipe soldered joint H Condenser process pipe soldered joint I Anti Dew pipe soldered joint Fig 8 Built in condenser Fig 9 ...

Page 14: ...r fault and it should be repaired or replaced 2 If compressor s shock absorption rubber is hardening or damaged or fixing screw of compressor is too tight or loose it will cause noise The settlement is to change new shock absorption rubber or adjust fixing screws Fan noise 1 Normal fan motor and airflow should not exceed 32dB 2 If there is noise above 32 dB or the noise levels fluctuate the fan sh...

Page 15: ...Fig 11 1 5 Re assemble the unit Refrigerant jet noise If there is continuous noise like a water spray from the capillary the end of capillary is in the wrong position or there are rough edges on the end of the capillary 1 Heat the soldered joint of the capillary A of Fig 8 and Fig 9 Fig 9 1 then remove the capillary from the evaporator and smooth the end with an eraser Caution Do not allow any par...

Page 16: ... evaporator if the ice is allowed to get too thick it may damage the fan 1 Ensure door is sealed against the frame if there is slight distortion of the seal heat the effected area gently with a hair dryer genrly see fig 12 with smooth strokes of the hair dryer then when still warm pull the effected area back into its original position this process may have to be repeated until the seal is complete...

Page 17: ...ix the wire in the correct position using the cable clip with screw Fig 15 Fig 14 Fig 15 5 If fan is foult please relace the whole fan 6 Note the upper method only for the connector fixed under the evaporator ...

Page 18: ...time d The condenser and evaporator fans Some models do not have evaporator fan work at full speed e The switch which controls the light functions normally 3 If the control panel and the various components of the unit do not respond as above Check the faulty part and relevant connection If this does not cure the fault replace the control board see Fig 18 Fig 19 4 If you return the control panel to...

Page 19: ...plays E3 E4 it indicates the sensor E3 E4 should be replaced the anti frost sensor under the evaporator The replacement method is as same as below Since the location of sensor on the old model is difference check the sensor as below 1 Normally the LED temperature display should the ambient temperature shortly after the unit is plugged in if not disassemble the electrical box see Fig 18 Fig 19 chec...

Page 20: ... the control board and replace the control board see Fig 19 5 Remove the two transformer fixing screws and replace the transformer 6 Fig 19 6 To replacing the display board Pull the four 4 display cover 8 fasteners as per arrowhead direction and then remove the display board and its two connectors from both sides Replace the display board See Fig 19 The dismantlement method of the electrical box s...

Page 21: ...f the PCB board replace it with the same model s PCB board Fig 19 Fig 19 Fig 20 Diagram of the main PCB Fig 20 1 To display PCB connect to 8 2 To display PCB connect to 9 3 To evaporator sensor Red 4 To inner sensor White 5 To LED light White 6 To power PCB White 7 To outer fan Yellow B How to replace the power PCB and transformer ...

Page 22: ... B take off the tranformer B for replacement Fig 35 Divide version control panel connections Fig 21 Fig 21 Fig 22 Diagram of the power PCB Fig 22 1 To PCB heater white 2 To main PCB white 3 To out fan Red 4 To compressor 5 Connectors of the power N 6 Connectors of the power L 7 Transformer primary connector 8 Transformer secondary connector How to replace the light 1 How to replace the bulb a Remo...

Page 23: ...ds one by one take the LED light upward replace it Fig 24 Fig 24 How to replace the decorative frame Remove the screw 1 2 3 pull the decorative frame according to the arrowhead that view K show then remove the screw 4 5 6 from the gap betoween decorative frame and cabinet remove the decorative frame Fig 25 ...

Page 24: ...18 Fig 25 ...

Reviews: