Supervisory Pressure Switch
A supervisory pressure switch will always be located on the primary cylinder by the Primary Actuator Kit
(PAK). For secondary cylinders, this is an optional component that may be added on. For primary
cylinders, the pressure switch is mounted on the primary actuator kit. For all secondary cylinders, the
pressure switch is mounted on the Schrader fitting on the cylinder valve.
1. Remove cap from applicable Schrader fitting.
2. Thread the switch onto the Schrader using the brass wrench flats only.
Figure 17 - Supervisory Pressure Switch Installation
NOTE: Pressure switches do not contain any field replaceable parts. Refer to applicable control
panel manual for wiring of the supervisory pressure switch. Wire in accordance with local and
national electrical codes.
The electrical rating is rated to 5A resistive and 3A inductive at 30V DC; gold flashing over silver contact for
loads down to 1mA at 24V DC.
Supervisory pressure switches are connected in parallel to the control panel supervisory input.
WARNING!
Proof pressure (*) limits stated on the nameplate must never be exceeded, even by surges in the
system. Occasional operation of unit up to proof pressure is acceptable (e.g., start-up, testing).
Continuous operation should not exceed the designated over range pressure (**).
*Proof pressure - the maximum pressure to which a pressure sensor may be occasionally
subjected, which causes no permanent damage (e.g., start-up, testing).
**Over Range Pressure - the maximum pressure to which a pressure sensor may be continuously
subjected without causing damage and maintaining set point repeatability.
WARNING!
Disconnect all supply circuits before wiring pressure switch. Electrical ratings stated in literature
and on nameplate must not be exceeded - overload on a switch can cause failure on the first cycle.
Wiring Color Code
Red
Black
White
Terminals
NO (NC under Pressure)
NC (NO under Pressure)
Com
1
2
4
3
1. Supervisory Pressure Switch (Primary)
2. Wrench Flats
3. Supervisory Pressure Switch (optional)
4. Schrader Valve Port