30
Charcoal Charbroiler (Natural/Mesquite)
ADP Nozzle mounted 24” minimum to 48” maximum from the midpoint of the cooking surface to the nozzle
tip, at an angle of 45° or more from the horizontal, aimed at the midpoint of the cooking surface.
Depth of the charcoal is limited to 6” maximum. Mesquite logs or wood are not acceptable.
NOTE: Appliance Drop Fittings Must Not be Sealed with Pipe Dope or Teflon Tape.
Figure 30 - Charcoal Charbroiler
AN ADP NOZZLE MAY BE LOCATED
ANYWHERE WITHIN THE GRID
DIAGONAL FROM
AIM POINT
48 in. (1219 mm)
MAX.
48 in. (1219 mm)
MAX.
48 in. (1219 mm)
MAX.
24 in. (610 mm) MAX.
24 in.
(610 mm)
MAX.
24 in.
(610 mm)
MAX.
6 in. (152 mm)
MAX. FUEL
AIM POINT: MIDPOINT
OF HAZARD AREA
AN ADP NOZZLE MAY BE
LOCATED ANYWHERE
WITHIN THE GRID
AIM POINT:
MIDPOINT OF
HAZARD AREA
24 in. (610 mm) MAX.
APPLIANCE AREA
NOZZLE LOCATION
45
o
OR MORE FROM
HORIZONTAL
SIDE VIEW
6 in. (152 mm)
MAX. FUEL
FRONT VIEW
24 in.
(610 mm) MIN.
48 in. (1219 mm) MAX.
Summary of Contents for EWC