36
Notes:
1. The combined total linear pipe (supply, overlapping branches, and ADP nozzle branches) must not
exceed 50'.
2. Max Supply Line Pipe can be increased from the values above if the total combined overlapping and
ADP branches are reduced by a corresponding amount.
3. Individual branch limitations must be maintained per the UL/ULC listed limits (e.g., max 5’ pipe & max
3 elbows for a dedicated ADP nozzle branch).
4. The notes from the UL/ULC listed single cylinder piping table must be followed (e.g., vertical rise,
splash requirements).
5. Duct or plenum branches may be substituted for dedicated ADP appliance branches per the above
table, provided the individual branch limitations are maintained per the UL/ULC listed limits (e.g., max
3’ pipe & max 2 elbows for an individual duct/plenum branch).
6. The R nozzle provides a wider spray angle than the ADP nozzle, the nozzles are identical in flow
points and flow rate. Therefore, the R nozzle may be used as a substitute for the ADP nozzle for low-
proximity range protection.
Table 8 - Single Cylinder with Additional ADP Nozzles (Recommended)
TF Nozzle
Qty
ADP Nozzle
Qty
Max Total
System Pipe
Max Supply
Line Pipe
Max Total
Overlapping
Branch Pipe
Max Total
Appliance
Branch Pipe
Max Total
Overlapping
Branch
Elbow
Max Total
Appliance
Branch
Elbows
Max Total
Combined
Branch
Elbows
1
4 Max
50’
26.5’
3.5’
20’
2
8
10
0
6 Max
50’
20’
0
30’
0
10
10