39
Nozzles
Distribution piping and nozzles are factory-installed. Verify that the nozzles and distribution network are
installed in accordance with the design and installation parameters for all protected hazards, as set forth in
this manual.
NOTE: The EWC extinguishing system design must be reviewed if any hazard changes have been
made, including (but not limited to): appliance type, appliance sizes, appliance location, factory
pre-piping or nozzles, plenum size or configuration, and duct size or configuration.
1. Ensure nozzles are installed without Teflon tape or pipe compound.
2. Ensure nozzles are securely installed. DO NOT OVERTIGHTEN.
3. Ensure nozzle seals are properly oriented in the nozzle cap. The seal must be installed with the brass
retaining ring (attached to the foil seal) facing towards the nozzle.
4. Ensure nozzle caps and foil seals are installed on each nozzle and secure. Nozzle caps should be
wrench-tightened 1/4 to 1/2 turn past hand-tight.
NOTE: Do not over-tighten or foil seals could be damaged.
5. Ensure all nozzle types, placement, and aim are in accordance with the limitations in this manual.
Optional nozzle swivel adapters can be used to achieve proper aim on dedicated appliance protection
nozzles only.
6. Refer to
on
for details on nozzle(s).