43
Fire Protection Manual Actuation Device
Figure 37 - Activation Device
The push/pull station is a remote manual actuation device to activate the
fire system. This remote manual actuation device (push/pull station)
contains one set of normally open contacts and mounts to any standard
single gang junction box. When the front button is pressed, the electrical
connection to the fire system is completed, thus activating the fire system.
The remote manual actuation device (push/pull station) should be
mounted at a point of egress and positioned at a height determined by the
Authority Having Jurisdiction (AHJ). This position is usually 10 to 20 feet
from hood and 42 to 48 inches above the floor. Multiple remote manual
actuation devices (push/pull stations) are acceptable to use in the fire
system and are wired in parallel per the electrical schematic. The remote
manual actuation device (push/pull station) is reset by twisting the push-
button clockwise until the internal latch is released.
The clear protective cover must be installed to protect the device from accidental activations. This cover is
provided as part of the manual actuation device. Below are the part numbers for the devices and
replacement parts.
Note: When connecting the wires to the push/pull station, do not twist the wire ends together.
Insert each wire on the opposite side of the screw.
Trouble Input Wiring
Trouble contacts and supervision switches from each device should be connected to the trouble input of
the building fire alarm panel to indicate a trouble condition.
Figure 38 - Wiring Connection for Trouble Contact
Table 14 - Activation Device Part Numbers
Part Description
Part Number
Push-Button with Clear Cover
STI-SS2431
Push-Button with Clear Cover and Horn
STI-SS2441
Replacement Clear Cover
STI-COVER
Blue Extension for Surface Mounted Push Stations
SF-1331
Blue Junction Box with Deep Back
STI-KIT71101AB
Normally Open Contact
STI-10196
Normally Closed Contact
STI-10198
Contact Housing Assembly
SF-10197H
PUSH
1. Building Fire Alarm
2. CORE Control Panel Trouble Contact
3. End of Line Device
4. Building Fire Alarm - Trouble Input Wiring
TBC
TBL
TOK
1
4
2
3