55
TROUBLESHOOTING
lists out causes and corrective actions for possible problems with the system. Review this list
prior to consulting manufacturer.
Table 19 - Fire Protection System Troubleshooting
Problem
Potential Cause
Corrective Action
Exhaust Fan On and Supply Fan
will not Start
Broken supply fan belt
Replace fan belt.
Fire system not armed
Fire system distributor must arm
fire system.
Fire System Activated Light On
Fire system is activated
Verify fire is out and reset fire
system.
Audible Alarm is On
Fire system is activated
Verify fire is out and reset fire
system.
A fault code is flashing on the
“Fire System Activated” light
A fault has been detected in the
Fire Protection System
Count the flashes and refer to
Fire System will not turn off
Duct sensor is hot
Heat has activated the duct
sensor. Remove heat source or let
the system extinguish the fire.
Once heat source or problem is
resolved, press reset button on
the face of the electrical control
package.
Remote Manual Actuation Device
has been pushed
Reset remote push station once
fire is out and press reset button
on the face of the electrical control
package. Reset remote push
station by twisting clockwise until
reset.
Gas Valve does not close
Debris on gas valve seal
Fully clean gas valve and strainer.