14
Primary Actuator Kit (PAK)
Figure 16 - Actuator Valve Set Position
The primary actuator kit is mounted to the primary cylinder
bracket during shipment and when testing the system. With the
cylinders securely mounted and connected to the system
piping, the primary actuator kit can be installed onto the
primary cylinder for the final setup.
1. Remove the valve protection plate and nuts. Retain the
mounting bolts for installation of the PAK.
2. Ensure the primary actuator piston is in the set position.
3. Loosen the PAK shipping bolts from the top of the bracket,
slide the unit back and lower it into position on the valve
actuation flange.
4. Insert the mounting bolts through the bottom of the valve
flange into the PAK mounting holes and tighten securely.
5. Connect the primary actuator hose to the Schrader valve
port on the primary cylinder valve. The primary hose
requires a 1.5” minimum bend radius.
Secondary Valve Actuator
With the cylinders securely mounted and connected to the system piping, the secondary valve actuators
(SVA) can be installed onto each of the secondary cylinder(s).
1. Remove the valve protection plate and nuts. Retain the mounting bolts for installation of the SVA.
2. Loosen the SVA shipping bolts from the top of the bracket, slide the unit back and lower it into position
on the valve actuation flange.
3. Insert the mounting bolts through the bottom of the valve flange into the SVA mounting holes and
tighten securely.
4. Ensure the secondary actuator hose is securely connected to the primary actuator output port and
SVA input port.
Key Limitations
•
Total length of secondary actuation flex hose must not exceed 75” of flex hose, refer to
Valve Actuator (SVA) and Hose” on page 9
for secondary hose information.
•
Secondary actuator hose(s) require 1” minimum bend radius.
•
Maximum number of secondary valve actuators operating from the primary actuator unit is three (3).
WARNING!
Installation of the primary actuator hose is the FINAL step performed.
Connecting this hose earlier may result in accidental system discharge. Refer to “Start-up/Test
Procedure” on page 60 for the testing and commissioning procedure.
The primary and secondary actuation hoses cannot be interchanged. The primary actuation hose
must be used with the PAK.
WARNING!
The Valve Protection Plate must remain on the valve actuation port until the valve actuator is
installed.
The primary and secondary actuation hoses cannot be interchanged. The secondary actuation
hose (7", 24" or 60" length) must be used with secondary valve actuators.