Attention:
Programming the advanced features of this operator must only be undertaken by fully
trained and qualified personnel. Please contact your dealer for details.
M
ENU
O
VERVIEW
<
:
a
Add beam break (photocell)
b
Set maximum OPENING force
c
Set maximum CLOSING force
d
Set offset learned power limit (sensitivity)
e
Set start-up phase
f
Set "operator speed"
<
A
DVANCED SETTINGS
☞
Advice:
The values for the automatic cut-out (= max. force) and learning power limit (= power
curve) can be set manually in the 2nd programming level.
A setting should always be carried out as soon as a less sensitive setting has to be chosen
due to door travel properties caused by site conditions, as otherwise the automatic cut-out
or power limit would react and cause malfunctions.
In general you have to take care that the allowed operating forces according to EN 12445
and EN 12453 are not exceeded.
☞
Advice:
The setting of the automatic cut-out corresponds to the maximum power of the operator.
At the first travel to OPEN or CLOSE direction after 'POWER ON' the automatic cut-out
is effective according to the adjustment. For further travels the self-learned power, that is
more sensitive, is effective. The automatic cut-out is still the upper limit of power.