11
“UE BASIC” +08C0042EZ - rel. 1.0 - 16.10.2017
ENG
Hydraulic interfaces dimensions
Interfaces dimensions
drain/fill
dimensions
mm (inc)
UE005 to UE015
D
72.6 (28.6)
D’
125.4 (49.4)
E
52.6 (20.7)
E’
107.5 (42.3)
Interfaces dimensions
steam outlet and condensed
drain
dimensions
mm (inc)
UE005 to UE015
F
126.7 (50.0)
F’
224 (88.2)
G
137.9 (54.3)
G’
21.7 (8.6)
Interfaces dimensions
drain/fill
dimensions
mm (inc)
UE025 to UE065
I
40 (15.8)
I’
72 (28.3)
I’’
10.2 (4.0)
L
123.2 (48.5)
L’
231.2 (91.0)
L’’
49.1 (19.3)
Interfaces dimensions
steam outlet and condensed
drain
dimen.
mm
(inc)
UE025 to
UE045
UE065
M
172 (67.7) 223.7 (88.1)
M’
30.2 (11.9) 30.2 (11.9)
N
181 (71.3) 181 (71.3)
N’
--- 100
(39.4)
N’’
55 (21.7)
61 (24.0)
2.1 Supply
water
Only use mains water with:
•
pressure between 0.1 and 0.8 MPa (14.5 and 116 PSI), temperature
between 1 and 40 °C (33.8 and104 °F) and an instant flow-rate no lower
than the rated flow of the fill solenoid valve, the connection is G3/4M
(see par. “11.2 Technical specifications”);
•
hardness no greater than 40 °f (equal to 400 ppm of CaCO
3
),
conductivity: 75 to 1250 μS/cm;
•
no organic compounds.
supply water
characteristics
unit of
measure
normal
water
water with low
salt content
min.
max.
min.
max.
Hydrogen ions (pH)
7
8.5
7
8.5
Specific conductivity at
20°C (
σ
R, 20 °C
)
μS/cm
300
1250
75
350
Total dissolved solids (c
R
)
mg/l
(
1
)
(
1
)
(
1
)
(
1
)
Dry residue at 180°C (R
180
)
mg/l
(
1
)
(
1
)
(
1
)
(
1
)
Total hardness (TH)
mg/l CaCO
3
100
(2)
400
50
(2)
150
Temporary hardness
mg/l CaCO
3
60
(3)
300
30
(3)
100
Iron + Manganese
mg/l Fe+Mn
=
0,2
=
0,2
Chlorides
ppm Cl
=
30
=
20
Silica
mg/l SiO
2
=
20
=
20
Residual chlorine
mg/l Cl-
=
0,2
=
0,2
Calcium sulphate
mg/l CaSO
4
=
100
=
60
Metallic impurities
mg/l
0
0
0
0
Solvents, thinners,
detergents, lubricants
mg/l
0
0
0
0
Tab. 2.a
(1)
= values depend on the specific conductivity; in general:
TDS
#
0,93 * σ
R, 20 °C
;
R
180
#
0,65 * σ
R, 20 °C
(2)
= not less than 200% of the chloride content in mg/l CL
(3)
= not less than 300% of the chloride content in mg/l CL
-
There is not reliable relationship between hardness and conductivity of
the water
Important:
•
do not treat the water with softeners, this may cause the entrainment
of foam, affecting the operation of the unit;
•
do not add disinfectants or anticorrosive compounds to the water, as
these are potential irritants;
•
the use of well water, industrial water or water from cooling circuits
and, in general, any potentially chemically or bacteriologically
contaminated water is not recommended.
2.2 Drain
water
this contains the same substances dissolved in the supply water, however
in larger quantities;
•
it may reach a temperature of 100 °C (212 °F);
•
it is not toxic and can be drained into the sewerage system.