18
“UE BASIC” +08C0042EZ - rel. 1.0 - 16.10.2017
ENG
(**) To display the alarm log (HYS
) press:
•
ENTER (the most recent alarm is shown)
•
UP or DOWN to scroll the list of alarms in chronological order
press ESC to return to the main screen
To delete the list of alarms press UP and DOWN for 5 seconds (inside the
alarm log), when the list has been reset the display will show ‘res’.
(***) To modify the humidification differential (P1) press:
•
ENTER (display:
)
•
UP or DOWN to modify humidification differential value (from 2 to
19.9)
•
ENTER to confirm the new value
Press ESC to return to the main screen
Parameter P1 can also be accessed from the list of parameters (see chap. 7).
(****) To modify outlet set point (st) press:
•
ENTER (display:
)
•
UP or DOWN to modify the set point (from 0 to 100)
•
ENTER to confirm the new value
Press ESC to return to the main screen
Parameter “st” can also be accessed from the list of parameters (see chap. 7).
6.6 Disabling
The humidifier can be disabled in 3 different ways:
•
Opening contact M2.4 and M2.5 (enable) : the display shows C--
•
From serial (see Chap. 7 Digital 2) : the display shows S--
•
From terminal (see ESC button) : the display shows t--
6.7 Recalling the manufacturer defaults
From the main screen press ENTER until the password screen is shown:
•
Enter the password 50
•
The message dEF is displayed, flashing
Confirm by pressing ENTER or exit by pressing ESC
If no button is pressed for 30 seconds, the display returns to the main
screen.
6.8 Display software release
1) when switching on the unit to display “rel. x.y “(example rel. 1.2)
2) during operation
a) display: from main screen press ESC and UP appear in sequence:
the size dell’umidificatore, the voltage, the number of phases and the
software release
b) via network using integer variable 81. Format = # # #. # “(e.g. 12 =
release 1.2)”.
6.9 Match digit (match between the
softwares of board and terminal)
humiSteam basic verifies the matching between the softwares of the
controller and the terminal at the start-up. The 8th digits for board and
9th for terminal of both codes must be equal.
If there is no match, on power-up after displaying the software release, and
in normal operation when pressing UP+PRG, the red LED will remain on for 5
seconds, and the following error message will be displayed:
“X – Y”, where “X” and “Y” are the 2 different 8th digits. Refer to the after-
sales service.
6.10 Reset cylinder hour counters
•
Access parameter ‘da’ (see chap. 7)
•
press UP and DOWN for 5 seconds
When the counter has been reset, the display shows ‘res’ .
6.11 Parameters: Saving/recalling the user
settings
From the main screen, a copy of the user settings can be saved at any
time, and then later recalled.
To save the settings::
From the main screen press:
•
ENTER for 2 seconds,
•
enter the password 51 using the UP or DOWN button and press ENTER, the
message UbP (Backup User parameters) flashes
•
press ENTER: the message -L- is displayed, flashing
•
press UP or DOWN, the message–S- (Save) is displayed, flashing,
•
press ENTER to save a copy of the user settings, or press ESC to cancel the
operation
NOTE: the copy of the user parameters saved previously will be
overwritten with current user settings.
To recall the settings::
From the main screen press:
•
ENTER for 2 seconds,
•
enter the password 51 using the UP or DOWN button and press ENTER,
the message UbP (Backup User parameters) flashes
•
press ENTER: the message -L- (Loading) is displayed flashing,
•
press ENTER to recall the previously saved copy of the user settings, or
press ESC to cancel the operation.
If no button is pressed for 30 seconds, the display returns to the main
screen, without performing the operation.
6.12 Manually drain the water in the cylinder
Total drain on power-up
Switch on the humidifier while holding UP and DOWN until the cylinder
and drain symbols are shown (the message ‘dr’ on the display alternating
with ‘tot’ indicates the function has been activated). To stop the function
before completion press UP and DOWN for 5 seconds
Total drain in operation
Press UP and DOWN together for 2 seconds (the message ‘dr’ on the
display alternating with ‘tot’ indicates the function has been activated).
Press UP and DOWN again for 2 seconds to stop the drain cycle. The
drain cycle in any case ends automatically.