CAREL INDUSTRIES HQs
Via dell’Industria, 11 – 35020 Brugine – Padova (Italy) - Tel. (+39) 0499716611 – Fax (+39) 0499716600 – e-mail: carel@carel.com –
www.carel.com
“UEX trifase - Power connections” +050004274 - rel. 1.0 - 12.01.2021
Nota:
attenzione al corretto inserimento dei
cavi. Se utilizzato un cacciavite manuale porre atten-
zione al corretto serraggio delle viti. Se utilizzano un
cacciavite elettrico, tenere la coppia di serraggio al
minimo e poi ripassare con un cacciavite a mano per
fissare definitivamente le viti.
Note:
make sure the cables are correctly. If
using a manual screwdriver, ensure the screws are ti-
ghtened correctly. If using a power screwdriver, set
the tightening torque to the minimum and then ti-
ghten the screws completely using a manual screw-
driver.
Note:
veillez à insérer correctement les câbles.
Si vous utilisez un tournevis manuel, veillez à bien ser-
rer les vis. Si vous utilisez un tournevis électrique,
maintenez le couple de serrage au minimum et utili-
sez ensuite un tournevis manuel pour fixer les vis de
façon définitive.
Hinweis:
Achtung auf das korrekte Einführen der
Kabel. Bei Verwendung eines Handschraubendrehers
muss auf das richtige Drehmoment der Schrauben ge-
achtet werden. Bei Verwendung eines elektrischen
Schraubendrehers muss das Drehmoment auf dem
Minimum gehalten werden, und die Schrauben müss-
en zum Schluss mit einem Handschraubendreher
fixiert werden.
Nota:
preste atención a la correcta introducción
de los cables. Si se utiliza un destornillador manual, pre-
ste atención al correcto apriete de los tornillos. Si se
utiliza un destornillador eléctrico, mantenga el par de
apriete al mínimo y luego repase con un destornillador
manual para fijar definitivamente los tornillos.
Fixing the contactor on the bracket with 4
screws M4x80 included on kit
KITCONT101SP - KITCONT102SP
Assembly
Fastening torque
1
2
Contacts
KITCONT101SP M 3,5 - 1,5 N.m Ø 5,5
po
zidr
iv N° 2
KITCONT102SP M 4 - 2,5 N.m
Ø 6,5
Coil
KITCONT101SP
KITCONT102SP
M 3,5 - 1,2 N.m Ø 5,5
Disassembly
1
2
KITCONT103SP - KITCONT107SP
Assembly
Fastening torque
CLICK !
1
2
Contacts
KITCONT103SP
KITCONT107SP
M 6 - 4 N.m
Ø 6,5
po
zidr
iv N° 2
Coil
KITCONT103SP
KITCONT107SP
M 3,5 - 1,2 N.m Ø 5,5
Disassembly
1
2
KITCONT108SP
Note: DO NOT
use the supplied
DIN-RAIL
Assembly
Disassembly
CLICK !
1
2
1
2
Fastening torque
Contacts
KITCONT108SP M 8 - 6 N.m
-
hexagon
4mm
Coil
KITCONT108SP M 3,5 - 1,2 N.m
Ø 5,5
po
zidr
iv
N° 2
KITCAUX000SP
AUX-contact Assembly
AUX-contact Disassembly
1
2
2
CLICK !
1
2
Fastening torque
AUX-Contacts
KITCAUX000SP M 3,5 - 1,52 N.m
Ø 5,5
po
zidr
iv
N° 2
KITCONT113SP
Assembly
Fastening torque
5 mm
Contacts
M 6 -
9 N.m
-
Ø 5,5
po
zidr
iv N° 2
AUX-
Contact
-
M 3,5
1 N.m
Ø 5,5
Coil
-
M 3,5
1 N.m
Ø 5,5
Disassembly:
unscrew the 4 screws M4x80
Models
Power
supply (V)
Phase contactor spare parts
UE001*(1)U* 208
1 ph
KITCONT101SP
UE001*(1)D* 230
1 ph
KITCONT101SP
UE003*(1)U* 208
1 ph
KITCONT101SP
UE003*(1)D* 230
1 ph
KITCONT101SP
UE003*(1)W* 208
3 ph
KITCONT101SP
UE003*(1)K*
230
3 ph
KITCONT101SP
UE003*(1)L*
400
3 ph
KITCONT101SP
UE003*(1)M* 460
3 ph
KITCONT101SP
UE003*(1)N* 575
3 ph
KITCONT101SP
UE005*(1)U* 208
1 ph
KITCONT102SP
UE005*(1)D* 230
1 ph
KITCONT102SP
UE005*(1)W* 208
3 ph
KITCONT102SP
UE005*(1)K*
230
3 ph
KITCONT102SP
UE005*(1)L*
400
3 ph
KITCONT101SP
UE005*(1)M* 460
3 ph
KITCONT101SP
UE005*(1)N* 575
3 ph
KITCONT101SP
UE008*(1)W* 208
3 ph
KITCONT102SP
UE008*(1)K*
230
3 ph
KITCONT102SP
UE008*(1)L*
400
3 ph
KITCONT101SP
UE008*(1)M* 460
3 ph
KITCONT101SP
UE008*(1)N* 575
3 ph
KITCONT101SP
UE009*(1)U* 208
1 ph
KITCONT103SP
UE009*(1)D* 230
1 ph
KITCONT102SP
UE010*(1)W* 208
3 ph
KITCONT102SP
UE010*(1)K*
230
3 ph
KITCONT102SP
UE010*(1)L*
400
3 ph
KITCONT101SP
UE010*(1)M* 460
3 ph
KITCONT101SP
UE010*(1)N* 575
3 ph
KITCONT101SP
UE015*(1)W* 208
3 ph
KITCONT106SP
UE015*(1)K*
230
3 ph
KITCONT102SP
UE015*(1)L*
400
3 ph
KITCONT102SP
UE015*(1)M* 460
3 ph
KITCONT102SP
UE015*(1)N* 575
3 ph
KITCONT102SP
Models
Power
supply (V)
Phase contactor spare parts
UE018*(1)L*
400
3 ph
KITCONT102SP
UE018*(1)M* 460
3 ph
KITCONT102SP
UE018*(1)N* 575
3 ph
KITCONT102SP
UE025*(1)W* 208
3 ph
KITCONT107SP
UE025*(1)K*
230
3 ph
KITCONT107SP
UE025*(1)L*
400
3 ph
KITCONT102SP
UE025*(1)M* 460
3 ph
KITCONT102SP
UE025*(1)N* 575
3 ph
KITCONT102SP
UE035*(1)W* 208
3 ph
KITCONT108SP
UE035*(1)K*
230
3 ph
KITCONT108SP
UE035*(1)L*
400
3 ph
KITCONT103SP
UE035*(1)M* 460
3 ph
KITCONT103SP
UE035*(1)N* 575
3 ph
KITCONT103SP
UE045*(1) W* 208
3 ph
KITCONT113SP
UE045*(1)K*
230
3 ph
KITCONT113SP
UE045*(1)L*
400
3 ph
KITCONT107SP
UE045*(1)M* 460
3 ph
KITCONT107SP
UE045*(1)N* 575
3 ph
KITCONT107SP
UE065*(1)L*
400
3 ph
KITCONT108SP
UE065*(1)M* 460
3 ph
KITCONT108SP
UE065*(1)N* 575
3 ph
KITCONT108SP
UE090*(1)L*
400
3 ph
KITCONT108SP
UE090*(1)M* 460
3 ph
KITCONT108SP
UE090*(1)N* 575
3 ph
KITCONT108SP
UE130*(1)L*
400
3 ph
KITCONT108SP
UE130*(1)M* 460
3 ph
KITCONT108SP
UE130*(1)N* 575
3 ph
KITCONT108SP
(1)
X : UE001 .... UE130
Y : UE001 .... UE065
W : solo per UE065 versione L
Humisteam x-plus,Basic, Wellness
Heatersteam
Models
Power
supply (V)
Phase contactor spare parts
UR002*U*
208
1 ph
KITCONT101SP
UR002*D*
230
1 ph
KITCONT101SP
UR004*U*
208
1 ph
KITCONT101SP
UR004*D*
230
1 ph
KITCONT101SP
UR006*U*
208
1 ph
KITCONT102SP
UR006*D*
230
1 ph
KITCONT102SP
UR006*W*
208
3 ph
KITCONT101SP
UR006*K*
230
3 ph
KITCONT101SP
UR006*L*
400
3 ph
KITCONT101SP
UR006*M*
460
3 ph
KITCONT101SP
UR006*N*
575
3 ph
KITCONT101SP
UR010*W*
208
3 ph
KITCONT102SP
UR010*K*
230
3 ph
KITCONT101SP
UR010*L*
400
3 ph
KITCONT101SP
UR010*M*
460
3 ph
KITCONT101SP
UR010*N*
575
3 ph
KITCONT101SP
UR013*K*
230
3 ph
KITCONT102SP
UR013*L*
400
3 ph
KITCONT101SP
UR013*M*
460
3 ph
KITCONT101SP
UR013*N*
575
3 ph
KITCONT101SP
UR020*W*
208
3 ph
KITCONT103SP
UR020*K*
230
3 ph
KITCONT103SP
UR020*L*
400
3 ph
KITCONT102SP
UR020*M*
460
3 ph
KITCONT102SP
UR020*N*
575
3 ph
KITCONT102SP
UR020*P*
690
3 ph
KITCONT101SP
UR027*K*
230
3 ph
KITCONT103SP
UR027*L*
400
3 ph
KITCONT102SP
UR027*M*
460
3 ph
KITCONT102SP
UR027*N*
575
3 ph
KITCONT102SP
UR027*P*
690
3 ph
KITCONT101SP
UR040*L*
400
3 ph
KITCONT103SP
UR040*M*
460
3 ph
KITCONT103SP
Models
Power
supply (V)
Phase contactor spare parts
UR040*N*
575
3 ph
KITCONT103SP
UR040*P*
690
3 ph
KITCONT103SP
UR053*L*
400
3 ph
KITCONT107SP
UR053*M*
460
3 ph
KITCONT107SP
UR053*N*
575
3 ph
KITCONT107SP
UR053*P*
690
3 ph
KITCONT103SP
UR060*L*
400
3 ph
KITCONT107SP
UR060*M*
460
3 ph
KITCONT107SP
UR060*N*
575
3 ph
KITCONT107SP
UR060*P*
690
3 ph
KITCONT103SP
UR080*L*
400
3 ph
KITCONT108SP
UR080*M*
460
3 ph
KITCONT108SP
UR080*N*
575
3 ph
KITCONT108SP
UR080*P*
690
3 ph
KITCONT103SP
Assemblaggio nelle unità
UE*
ed UR*
Assembly in
UE * and UR *
units
Assemblage dans les unités
UE * et UR *
Montage in
EU * - und UR *
-Einheiten
Montaje en unidades
UE *
y UR *
Smaltimento del prodotto
L’apparecchiatura (o il prodotto) deve essere ogget-
to di raccolta separata in conformità alle vigenti
normative locali in materia di smaltimento
Disposal of the product:
the appliance (or the product) must be disposed of
separately in accordance with the local waste dis-
posal legislation in force.
Élimination du produit
L’équipement (ou le produit) doit faire l’objet
d’un ramassage particulier en conformité avec les
normes en vigueur locales en matière d’élimination
des déchets
Entsorgung des Produktes
Das Gerät (oder Produkt) muss im Mülltrennung-
sverfahren in Übereinstimmung mit den örtlichen
Entsorgungsnormen entsorgt werden.
Reciclage del producto
Los componentes (o el producto) deben ser trata-
dos separadamente en conformidad a la normativa
local vigente en materia de reciclaje
CAREL si riserva la possibilità di apportare
modifiche o cambiamenti ai propri prodotti senza
alcun preavviso
CAREL reserves the right to modify the features of
its products without prior notice.
CAREL se réserve la possibilité d’apporter des
modifications ou des changements à ses produits
sans aucun préavis.
CAREL behält sich das Recht vor an seinen eigenen
Produkten ohne Vorankündigungen Verbesserun-
gen oder änderungen vorzunehmen
CAREL se reserva la posibilidad de modificar o
cambiar las caractéristicas de sus productos, sin
previo aviso.