47
ENG
Control
WTS LARGE +0300131IT rel. 1.0 - 05.09.2022
11.6.6 Lower level switch LSLOW
With the aid of the level switch, the minimum fill level in
the permeate vessel can be monitored and the system
can be started automatically if the pressure falls below
the required level.
»
Select
5 LOW LEVEL
5 LOW LEVEL
6 HIGH LEVEL
»
Press the arrow keys
éê
to select if pressure
switch should be active or inactive.
5A LOW LEVEL
ENABLED
ENABLED= active
DISABLED = inactive (
not recommended)
»
Confirm the selection with
If the set point function has been activated, the
program jumps to submenu "5B".
5B LOW LEVEL
CONTACT N.O.
Press the arrow keys
éê
to set the switching
direction.
N.O. CONTACT = The input functions as a normally open
contact.
N.C. CONTACT = The input works as a normally closed
contact
»
Confirm the selection with
.
The program jumps to submenu "5C"
»
Default value: NC
5C INPUT DELAY
00Sec
»
Press the arrow keys
éê
to set the time of
delay
0 Sec = no delay
(see note at the end of the chapter)
»
Confirm the selection with
.
The program jumps back to the main menu.
11.6.7 Upper level switch LS
HIGH
The pressure switch can be used to control the
maximum level in the permeate vessel and stop
production when this level is reached.
»
Select
6 HIGH LEVEL
in the main menu
6 HI LEVEL
7 MIN PRESSURE
6A HI LEVEL
ENABLED
»
Press the arrow keys
éê
to select if relay
input should be active or inactive.
ENABLED= active (ex works)
DISABLED = inactive
»
Confirm the selection with
.
If the set point function has been activated, the
program jumps to submenu "6B".
6B HI LEVEL
CONTACT N.O.
Press the arrow keys
éê
to set the switching
direction.
N.O. CONTACT = The input functions as a normally open
contact.
N.C. CONTACT = The input works as a normally closed
contact
(not recommended)
»
Confirm the selection with
.
The program jumps to submenu "6C".
6C INPUT DELAY
00Sec
»
Press the arrow keys
éê
to set the time of
delay
0 Sec = no delay
(see note at the end of the chapter)
»
Confirm the selection with
.
The program jumps back to the main menu