53
ENG
Control
WTS LARGE +0300131IT rel. 1.0 - 05.09.2022
11.6.17
Change password
In this submenu you can change the password to
program the main menu.
17 SET PASSWORD
18 MAINTENANCE
OLD PASSWORD
0000
»
Press the arrow keys
éê
to enter your latest
password
»
Confirm the selection with
.
If the entry is correct, the program displays "PASSWORD
ACCEPTED" and jumps to the next submenu.
NEW PASSWORD
0000
»
Press the arrow keys
éê
to enter your new
password
»
Confirm the selection with
.
The program jumps to the screen:
CONFIRM
0000
Press the arrow keys
éê
to enter your new password
again.
»
Confirm the selection with
.
The program jumps to the screen:
PASSWORD
CHANGED
If the entry is incorrect, "CONFIRM ERROR" appears on
the display for approx. 2 seconds before the programme
jumps back to the "NEW PASSWORD" input display so
that the new password can be entered again.
11.6.18
Reset password
To reset the password follow the steps below:
»
disconnect the unit from the power supply
»
press the two buttons
é
ESC
while
reconnecting the plug (connect to power
supply).
The display will show "RESET PASSWORD" for a few
seconds before the pump is started up.
11.6.19
Setting the maintenance
interval
In this submenu you activate the service interval and
enter the countdown of the service hour counter. In
the delivery status, the service hour counter is set to
00100 hours. (100 hours). Resetting the countdown is
described in submenu 13.
18 MAINTENANCE
19 DOSING PUMP
18A FAILED DO.
ENABLED
»
Press the arrow keys to activate or
inactivate the service hour counter
»
Confirm the selection with .
The program jumps to submenu "18B".
18B FAILED DO.
CONTACT N.C.
Press the arrow keys to enter the Service intervall in
hours
»
Confirm the selection with
.
The program jumps back to the main menu.
11.6.20
Dosing pump antiscalant
IN
PASC
If a dosing pump for the dosing of antiscalant is
installed instead of an upstream softening system,
then either the potential free fault signal output of the
dosing pump or the level switch (empty indicator) in
the dosing vessel can be connected to the controller.
If the INPASC input is switched, the control system can
switch off the RO system for the duration of the fault
and put it in the waiting mode. As soon as the fault
has been eliminated, the control system automatically
returns the RO system to production mode.
19 DOSING PUMP
20 STAND BY/ INPUT
19A FAILED DO.
ENABLED
»
Press the arrow keys
éê
to select if relay
input
should be active or inactive.
»
Confirm the selection with
.
The program jumps to submenu "19B".
»
Default value: DISABLED