54
ENG
Control
WTS LARGE +0300131IT rel. 1.0 - 05.09.2022
19B FAILED DO.
CONTACT N.C.
»
Press the arrow keys
éê
to set the switching
direction.
N.O. CONTACT = The input functions as a normally open
contact.
N.C. CONTACT = The input works as a normally closed
contact
»
Confirm the selection with
.
The program jumps to submenu "19C".
19C INPUT DELAY
00Sec
»
Press the arrow keys
éê
to set time of delay.
»
Confirm the selection with
.
The program jumps back to the main menu.
»
Default value: 00 sec
11.6.21
Stand-by-Input IN
SB
(Release
contact)
20 STAND BY / INPUT
21 PUMP DELAY
20A STAND BY IN
ENABLED
»
Press the arrow keys
éê
to select if relay
input should be active or inactive.
»
Confirm the selection with
.
The program jumps to submenu "20B".
»
Default value: DISABLED
20B STAND BY IN
CONTACT N.O.
»
Press the arrow keys
éê
to set the switching
direction.
N.O. CONTACT = The input functions as a normally open
contact.
N.C. CONTACT = The input works as a normally closed
contact
»
Confirm the selection with
.
The program jumps to submenu "20C".
20C INPUT DELAY
00Sec
»
Press the arrow keys
éê
to set the time of
delay
0 Sec = no delay
(see note at the end of the chapter)
»
Confirm the selection with
.
The program jumps back to the main menu.
11.6.22
Set start delay
20 STAND BY/ INPUT
21 PUMP DELAY
21A PUMP DELAY
00 sec
»
Default value: 00 sec
Notice:
Output activation / delay:
In order to avoid pipeline damage due to "water
hammer", a delay of 3 seconds between pump on (or
off ) and solenoid valve on (or off ) and a delay of 2
seconds between pump on (or off ) and pressure pump
on (or off ) has been set at the factory.
Summary of Contents for Large ROL 160-1K2
Page 2: ......
Page 6: ......
Page 43: ...43 ENG Control WTS LARGE 0300131IT rel 1 0 05 09 2022...
Page 59: ...59 ENG Spare parts WTS LARGE 0300131IT rel 1 0 05 09 2022 20 21 22 23 24 25 26 27 28 29 30...
Page 65: ...Notes...
Page 66: ...Notes...
Page 67: ......