10
ENG
“optiMist” +0300065EN - rel. 1.6 - 18/06/2021
1.6 Electrical specifications
EC*******0 (230 V 50 Hz) Modells
voltage
Vac
phases frequency
Hz
power
kW
current
A
EC005****0
230
1
50
0,275
1,2
EC010****0
230
1
50
0,275
1,5
EC020****0
230
1
50
0,475
1,6
EC040****0
230
1
50
0,475
2,3
EC080****0
230
1
50
0,75
3,0
EC100****0
230
1
50
0,75
3,2
Tab. 1.a
Product in compliance with EN55014, EN61000, EN60204.
Insulation grade III
Modelli EC*******U (230V 60 Hz)
voltage
Vac
phases frequ.
Hz
power
kW
current
A
FLA
SCCR
EC005****U 230
1
60
0,375
1,2
0.35 HP/2A 5 KA
EC010****U 230
1
60
0,375
1,5
0.35 HP/2A 5 KA
EC020****U 230
1
60
0,375
1,6
0.5 HP/3.2A 5 KA
EC040****U 230
1
60
0,375
2,3
0.5 HP/3.2A 5 KA
EC080****U 230
1
60
0,75
3,0
1 HP/6.0A 5 KA
EC100****U 230
1
60
0,75
3,2
1 HP/6.0A 5 KA
Tab. 1.b
Product in compliance with UL998
1.7 Opening the packaging
make sure the humidifier is intact upon delivery and immediately
notify the transporter, in writing, of any damage that may be due to
careless or improper transport;
move the humidifier to the site of installation before removing from
the packaging, grasping the neck only from underneath the base;
open the cardboard box, remove the protective material and remove
the humidifier, keeping it vertical at all times.
Store the packaging in a dry location (cardboard boxes, pallets, bolts and
fillers) so that they may be reused.
•
humidity 20-80% RH, non condensing
•
temperature 1-40 °C;
1.8 Positioning the cabinet
The humidifier should be positioned so as to guarantee the following:
•
open the front panel;
•
access to the inside parts for checks and maintenance;
•
connection of the water supply lines;
•
connection to the water distribution lines;
•
power and control connections;
Recommended clearance for routine maintenance:
•
from the front 1m;
•
right and left sides around 0.3 m.
Important: the maximum horizontal distance between the
cabinet and the distribution system/frame is:
1.
10 meters if discharge solenoid valves are used
2.
5 meters if mechanical solenoid valves are used (no mechanical valves
with EC005*);
3.
for larger distances, contact CAREL INDUSTRIES.
Positioning procedure:
•
after opening the packaging:
•
position the cabinet in the final position;
•
position the cabinet horizontally.
1.9 Wall mounting
Fasten the humidifier to a solid support surface using the screws and
bracket supplied.
Make sure there is enough space to connect the air and water inlet and
outlet lines.
Drilling for wall mounting
retro cabinet
38
20
38
20
38
20
20
38
554
Ø 6
790
669
Fig. 1.g
sezione staffe
38
20
38
20
38
20
20
38
554
Ø 6
790
669
Fig. 1.h