“optiMist” +0300065EN - rel. 1.6 - 18/06/2021
2. WATER CONNECTIONS
Important:
before making the connections, make sure that the
unit is disconnected from the mains.
CAUTION:
for the Australian market and to comply with
Watermark requirements, a watermarked approved dual check valve shall
be installed in the supply line to the humidifier when connected to
potable water. Should on the other hand the humidifier be fed with
treated water from a Carel reverse osmosis system connected to potable
water, the dual check valve shall be installed in the supply line to the
reverse osmosis system.
CABINET
1
2
4
5
6
8
water drain 3/4”f
water inlet 3/4”f
pressurized water G1/2”m
9
6
CABINET
1
2
water drain 3/4”f
water inlet 3/4”f
pressurized water G1/2”m
3
3
4
5
7
7
6
9
9
key:
1.
install a manual valve upstream
of the installation to allow
the water line to be isolated
(not supplied by CAREL);
2.
install a 10 µ water filter (CAREL
code ACKF000000 to remove
solid particles from the
supply water;
3.
flexible hose (not supplied by
CAREL);
4.
optiMist cabinet;
5.
hoses complete with adapters;
6.
nozzles (see Chap. 4);
7.
manifolds;
8.
manifold connection hoses;
9.
drain valves.
Fig. 2.a
N.B.:
for direct connection to the mains water supply use pipes
and fittings compliant with IEC 61770.
Connections:
1
2a
2b
3
Fig. 2.b
Key:
1. water inlet (G3/4” femmina);
2a. pressurised water outlet step 1 (G1/2” male);
2b. pressurised water outlet step 2 (G1/2” male);
3. tank-drain water (G3/4” female).
Notes for connection between cabinet and rack:
1.
Mount the pipes with u-bolts or clamps with steps of about 30 cm.
(not supplied by Carel).
2.
In the case of two racks or one two-step rack, mount the pipes
parallel, avoiding any contact.
3.
In laying the pipes, avoid conditions that could cause the water to
stagnate with the system is halted.
Connect an expansion tank (not supplied by CAREL SpA) with a capacity
of at least 5 litres, upstream from the cabinet in order to prevent water
hammering which can damage the system.
The connection to the cabinet must be performed using flexible piping.