3ODQW:DWFK
Cod. Carel. +030221221 – rel. 1.0 dated 20/02/01
32
6WDWXVVFUHHQURWDWLRQ
Enabling this parameter sets the automatic rotation of the screens, see paragraph “Automatic rotation of status screens”.
3DUDPHWHUV!)$;0RGHP
m1 m2 m3 m4
Modem config.
No Modem
Dialling: Tone
Type: PSTN
Data process centre
Enable call: Yes
0499716698
Test call: No
Data process centre
Change password
User Pass.:
00004 RemoteUser
Data process centre
Call to:
Send alarms: No
Download log: No
m5 m6 m7 m8
Fax configuration
A:04371234567
b:0123456789
c:0123456789
Test call fax
Fax service: A
Test call: No
GSM modem config.
PIN: 3241
SMS config.
Enable SMS send: Yes
SMS service centre
+393492000200
m9 m10 m11
SMS config. via PSTN
Pass:
Baud: 19200 UCP
Parity: None Bits: 8
SMS recipients
A:00393475272983
B:00393484427822
C:0039123456002
Send test SMS:
SMS Rec.: A
No
0RGHPFRQILJXUDWLRQ
The modem configuration screen includes the fields for selecting the port used to manage the modem, selecting the dialling
mode, pulse or tone, and configuring the type of modem. The options allowed for the port used are described in the following
table:
6HOHFWLRQ
3RUWXVHG
)XQFWLRQ
1RWH
No modem
RS232 serial
Direct supervisor connection in RS232 or
for setup via serial
External modem
RS232 serial
3Com-UsRobotics external modem
other model of modem can be used,
modifying the initialisation strings
using “
3ODQW:DWFKPDQDJHU
”
Internal modem
Internal serial
This selection is operative only if the model
of PlantWatch is PLW00M0000, for the
other models, it is the same as selecting
“External modem”
For each selection, the baud rate is fixed and equal to 115,200 baud, no parity, 2 stop bits.
The possible options for the type of modem are PSTN or GSM Type 1 and GSM Type 2; PSTN is for modems using dial-up
lines, while GSM is for cellphone modems, currently only the FALCOM A2, Siemens M20T and Wavecom WMOD2B can be
connected. The settings are:
Type 1
Falcom A2
Wavecom WMOD2B
ETM 9000
Type 2
Siemens M20T
The PSTN modems used must conform to the Hayes standard (AT.. commands) and support at least the V.34 (33600 baud)
standard; the pre-set model is Us-Robotics, other brands and models can be used by modifying the initialisation commands for
fax and data using “
3ODQW:DWFKPDQDJHU
”.