48
humiSteam -
cod. +030221910 rel. 5.2 - 07.11.2005
humiSteam - Parameter b1
FUNCTIONS
b1
DE-HUMIDIFICATION DILUTION DRAIN WITH
DRAIN WHEN NEW DEMAND
TOTAL DRAIN FOR
DISPLAY OF
ALARM RELAY
TOTAL PERIODICAL
REQUEST
CONTACTOR …
<= 2/3 CURRENT DEMAND
INACTIVITY
WARNINGS “CL” & “CP” ACTIVATED WHEN…
DRAIN
(CONTACTOR OPENED)
DEF. 0
OFF
OPEN
YES
ON, depending on bF
ON
ALARMS PRESENT
OFF
1
ON
OPEN
YES
ON, depending on bF
ON
ALARMS PRESENT
OFF
2
OFF
CLOSED
YES
ON, depending on bF
ON
ALARMS PRESENT
OFF
3
ON
CLOSED
YES
ON, depending on bF
ON
ALARMS PRESENT
OFF
4
OFF
OPEN
NO
ON, depending on bF
ON
ALARMS PRESENT
OFF
5
ON
OPEN
NO
ON, depending on bF
ON
ALARMS PRESENT
OFF
6
OFF
CLOSED
NO
ON, depending on bF
ON
ALARMS PRESENT
OFF
7
ON
CLOSED
NO
ON, depending on bF
ON
ALARMS PRESENT
OFF
8
OFF
OPEN
YES
OFF
ON
ALARMS PRESENT
OFF
9
ON
OPEN
YES
OFF
ON
ALARMS PRESENT
OFF
10
OFF
CLOSED
YES
OFF
ON
ALARMS PRESENT
OFF
11
ON
CLOSED
YES
OFF
ON
ALARMS PRESENT
OFF
12
OFF
OPEN
NO
OFF
ON
ALARMS PRESENT
OFF
13
ON
OPEN
NO
OFF
ON
ALARMS PRESENT
OFF
14
OFF
CLOSED
NO
OFF
ON
ALARMS PRESENT
OFF
15
ON
CLOSED
NO
OFF
ON
ALARMS PRESENT
OFF
16
OFF
OPEN
YES
ON, depending on bF
OFF
ALARMS PRESENT
OFF
17
ON
OPEN
YES
ON, depending on bF
OFF
ALARMS PRESENT
OFF
18
OFF
CLOSED
YES
ON, depending on bF
OFF
ALARMS PRESENT
OFF
19
ON
CLOSED
YES
ON, depending on bF
OFF
ALARMS PRESENT
OFF
20
OFF
OPEN
NO
ON, depending on bF
OFF
ALARMS PRESENT
OFF
21
ON
OPEN
NO
ON, depending on bF
OFF
ALARMS PRESENT
OFF
22
OFF
CLOSED
NO
ON, depending on bF
OFF
ALARMS PRESENT
OFF
23
ON
CLOSED
NO
ON, depending on bF
OFF
ALARMS PRESENT
OFF
24
OFF
OPEN
YES
OFF
OFF
ALARMS PRESENT
OFF
25
ON
OPEN
YES
OFF
OFF
ALARMS PRESENT
OFF
26
OFF
CLOSED
YES
OFF
OFF
ALARMS PRESENT
OFF
27
ON
CLOSED
YES
OFF
OFF
ALARMS PRESENT
OFF
28
OFF
OPEN
NO
OFF
OFF
ALARMS PRESENT
OFF
29
ON
OPEN
NO
OFF
OFF
ALARMS PRESENT
OFF
30
OFF
CLOSED
NO
OFF
OFF
ALARMS PRESENT
OFF
31
ON
CLOSED
NO
OFF
OFF
ALARMS PRESENT
OFF
32
OFF
OPEN
YES
ON, depending on bF
ON
ALARMS ABSENT
OFF
33
ON
OPEN
YES
ON, depending on bF
ON
ALARMS ABSENT
OFF
34
OFF
CLOSED
YES
ON, depending on bF
ON
ALARMS ABSENT
OFF
35
ON
CLOSED
YES
ON, depending on bF
ON
ALARMS ABSENT
OFF
36
OFF
OPEN
NO
ON, depending on bF
ON
ALARMS ABSENT
OFF
37
ON
OPEN
NO
ON, depending on bF
ON
ALARMS ABSENT
OFF
38
OFF
CLOSED
NO
ON, depending on bF
ON
ALARMS ABSENT
OFF
39
ON
CLOSED
NO
ON, depending on bF
ON
ALARMS ABSENT
OFF
40
OFF
OPEN
YES
OFF
ON
ALARMS ABSENT
OFF
41
ON
OPEN
YES
OFF
ON
ALARMS ABSENT
OFF
42
OFF
CLOSED
YES
OFF
ON
ALARMS ABSENT
OFF
43
ON
CLOSED
YES
OFF
ON
ALARMS ABSENT
OFF
44
OFF
OPEN
NO
OFF
ON
ALARMS ABSENT
OFF
45
ON
OPEN
NO
OFF
ON
ALARMS ABSENT
OFF
46
OFF
CLOSED
NO
OFF
ON
ALARMS ABSENT
OFF
47
ON
CLOSED
NO
OFF
ON
ALARMS ABSENT
OFF
48
OFF
OPEN
YES
ON, depending on bF
OFF
ALARMS ABSENT
OFF
49
ON
OPEN
YES
ON, depending on bF
OFF
ALARMS ABSENT
OFF
50
OFF
CLOSED
YES
ON, depending on bF
OFF
ALARMS ABSENT
OFF
51
ON
CLOSED
YES
ON, depending on bF
OFF
ALARMS ABSENT
OFF
Continues...
parameters for configuring the operation of accessory devices
code
range of
def.
unit of
description
disp.
variation
measure
b1
0, …, 127
0
See Tab. 7.3.3 Functions parameter b1
b2
0, …,120
0
s
shut-down delay time
b3
-10.0, …,10.0
0.0
%
current measurement gain
b4
0, ..., 199
water conductivity (0=automatic measurement)
0k2, ….2k0
0
µS/cm
b5
0, …, 199
1k0
µS/cm
conductivity pre-alarm threshold
0k2, ….2k0
b6
0, …, 199
1k3
µS/cm
conductivity alarm threshold
0k2, …, 2k0
b7
0, …, 100
50
%
foam detection threshold (0=exclude foam detect, 1=max sens., 100=min sens.)
b8
50, …, 200
100
%
internal conductivity reached by the cylinder in stable conditions against rated value
b9
50, ..., 200
100
%
adjust the duration of the drain for dilution
bb
0*, ..., 4000
1500
h
cylinder maintenance limit time (in hours)
0*= excluding life alarm “Cy” and the obligatory maintenance alarm “Mn”
100 hour step if bb>199 hours, hour step if bb<199 hours
bE
1, ..., 120
24
h
time limit between two periodical drain
accessible only if periodical draining is enabled
cycles
(weight 64 in “b1”)
bF
1, ..., 199
3
days
days to wait to drain due to inactivity
not accessible if draining due to
inactivity is disabled, weight 8 in “b1”
Tab. 7.3.2