8
ENG
“ultimateSAM - user” +0300070IE - rel. 1.0 - 23.05.2013
1.2.2
Dimensions and weights of the SA0
(single-pipe) distributor
“Y”
“X”
Fig. 1.b
The system used to identify the distributor is shown in Table 1.b. The table
shows the widths (dimension “X”) and heights (dimension “Y”).
SA
0
*
*
L
*
0
*
0
1
2
3
4
5
6
7
8
9
Tab. 1.c
1
ID prefi x
2
Feed type:
0
Single-pipe (single-upright)
3
Width:
Code Dimension “X” [mm (in)]
A
A = 503mm (19.7in)
B
B = 655 mm (25.7in)
C
C = 807 mm (31.7in)
D
D = 959 mm (37.7in)
E
E = 1111 mm (43.7in)
F
F = 1263 mm (49.7in)
G
G = 1415 mm (55.7in)
H
H = 1567 mm (61.7in)
I
I = 1719 mm (67.7in)
J
J = 1871 mm (73.7in)
K
K = 2023 mm (79.7in)
L
L = 2175 mm (85.7in)
Z
Z = 427 mm (16.8in) for SA0******* SMALL
4
Single-upright selec-
tion mm (in)
Code Dimension “Y” [mm (in)]
A
A= single upright 160 mm (6.3 in)
5
Type of upright (diame-
ter) mm (in)
L
L= 45 (1.75) OD
6
Insulation:
I
I = insulated uprights with nozzles
7
Frame:
0
0 = no frame, unassembled
8
Drain
U
U= ½ “ Male NPT
0
0= ½ “ Male Gas
Tab. 1.d
For other distances and measurements relating to the distributor see
the “Technical specifi cations” manual. See the remaining sections of this
manual for details on the other components of the ultimateSAM system.
1.3 Opening the packaging
•
Make sure the humidifi er is intact upon delivery and immediately
notify the transporter, in writing, of any damage that may be due to
careless or improper transport.
•
Open the shipping container and check contents for damage. If
the humidifi er is shipped unassembled, be sure to locate all of the
components.
•
Move the humidifi er to the site of installation before removing internal
packaging. For some installations, assembly may need to take place
inside the AHU.
NOTE: READ THE FOLLOWING SECTIONS ON POSITIONING
AND ASSEMBLY BEFORE PROCEEDING WITH INSTALLATION.
1.4 Assembling the SA*****2** frame
1.4.1
Assembling the frame, SAB/SAT versions
An unassembled frame is shipped with any SA*****2** ultimateSAM
distributor. The frame consists of the following:
-
2 bottom supports
(a)
(if a drain trap needs to be installed inside
the duct underneath the bottom manifold, the optional supports
may be required)
-
2 Side channels
(c)
;
-
4 Corner brackets
(d)
used on bottom feed system;
-
1 Top channel
(e)
used on bottom feed system;
-
2 Top brackets
(a)
used on top feed system;
-
Fasteners (M6x10 bolts with locking and fl at washers).
Assemble (but do not tighten) the following parts described in steps A-D,
using the fasteners provided:
a.
Fasten the bottom pedestals
(a)
to the bottom header
(b)
. The
choice of pedestal mounting position depends on the location of
the condensate drain for the bottom header.
-
If an elbow will be attached to the drain, use the mounting holes
for “standard position.” (Fig.1.c) This is the height at which factory-
assembled distributors are built (as pictured on the front cover).
-
If the drain will pass through a hole in the bottom of the duct, use
the mounting holes that provide minimum clearance (“minimized
position”).
-
If the drain is to be installed inside the duct or AHU, use the
optional mounting stand (SAKS010000) to provide up to 386mm
(15”) clearance. (Fig.1.d)
b.
Fasten the side channels
(c)
to the bottom pedestals
(a)
.
c.
If assembling a bottom feed system [SAB****2**], insert retaining
rings into the top channel of the frame. Fasten the corner brackets
to the side channels. Fasten the top channel to the corner brackets.
(Fig.1.e)
d.
If assembling a dual feed system [SAT****2**], fasten the top header
(f)
and brackets
(a)
to the side channels. (Fig.1.f ).
•
Tighten the screws with a tightening torque of 7-8 Nm (5-6 ft lb),
making sure that the components are assembled square;
a
b
37.5 mm
(1.48 in)
82.5 mm
(3.25 in)
Pedestal in
minimized position
Pedestal in
standard position
Fig. 1.c
g
236.6 mm
(9.31 in)
386.5 mm
(15.22 in)
Optional pedestal
in minimized position
Optional pedestal
in standard position
Fig. 1.d