residues.
l
exposure of the skin to a jet of hot steam may cause severe burns;
l
do not over-tighten the hose clamps (max. torque=180 N·cm).
2.1.2 Condensate hose
Follow these instructions when installing the condensate hose:
l
the condensate hose may be filled with hot water or steam: contact with the skin can cause serious
burns;
l
connect the hose to a drain in accordance with national and local regulations in force;
l
the condensate hose must have a minimum downward slope and must flow into a 200 mm high drain
trap: the drain trap must be at least 300 mm below the connection to the blower.
l
condensate drains must be installed at all the lowest points and wherever the drain line goes from
horizontal to vertical. The drain line must be connected to a “T” connector and have a minimum
downward slope. The drain trap must be at least 300 mm below the connection.
l
make sure that the condensate drain lines are not blocked;
l
do not over-tighten the clamps on the condensate hose.
Important:
before starting the humidifier, fill the drain traps with water.
Fig.2.b
ENG
VRDX030222195 rel. 1.2 – 22.03.2019
2. Preparing for assembly |