background image

Model 99FRD, 100CRD & 102CRD oil burners — Instruction manual

Carlin part number MN99102 Rev. 08/20/08

– 10 –

3.  Prepare burner 

(continued)

  Inspect the nozzle adapter before replacing the nozzle. If the 

threads have been damaged or show score marks, replace 
the nozzle line/adapter assembly.

4.  Replace the retention ring assembly by slipping one of the riveted arms 

through the gap between the electrode tips. Align this arm straight up, 
with the ring clamp firmly against the nozzle adapter shoulder (see 
Figure 10). Then tighten the clamping screw.

5.  Reposition and check the electrode settings. Position the electrodes as 

shown in Figure 10. These settings are critical in ensuring a reliable 
ignition. Once the electrodes are set, check all clamps to be sure they 
are securely tightened.

6.  Insert the combustion head/nozzle assembly in the burner.

Check zero position 

(99FRD & 100CRD only)

1.  See Figures 11, 12 and 13. Loosen the oil line thumb nut and adjusting 

slide locking screw. Use a 

B\cx

" Allen wrench to rotate the adjusting 

screw until the lead edge of the slide aligns to “0” on the scale. The 
retention ring should be flush, or nearly flush, with the edge of the 
throttling ring.

2.  If the retention ring is not close to flush with the throttle ring, make 

sure the air tube is completely inserted into the housing collar and the 

Set initial burner air settings

Combustion head
1.  The combustion head adjusting slide controls the spacing between the 

retention ring and throttle ring (or air cone), regulating how much air 
passes around the retention ring.

2.  Loosen the oil line thumb nut and adjusting slide locking screw. Use a 

B\cx

" Allen wrench to rotate the adjusting screw until the lead edge of 

the slide aligns to the number given in Table 3, page 11. Lock in place 
by first tightening the oil line thumbnut, then tightening the locking 
screw.

Air shutter
1.  The air shutter is fixed for all 99FRD, 100CRD and 102CRD burners. 

See page 7 for the correct air shutter type. (Some 102CRD burners 
may be equipped with 3-slot air shutters.)

Air band
1.  The air band is marked in percent opening. Loosen the air band locking 

screw and move the air band until the pointer lines up with the percent 
opening given in Table 3, page 11.

Final adjustments
1.  The burner is now adjusted to the approximate air settings for the firing 

rate chosen. When you check combustion with instruments during start-
up or servicing, you may have to adjust the head slightly to achieve the 
desired efficiency. See “Adjust burner using test instruments,” page 22. 
( Note that pressure overfire will reduce air flow, requiring more air 
opening.)

Figure 11

  Check zero position — 99FRD & 100CRD only

Figure 10

  Combustion head/nozzle/electrode settings

Figure 12

  Combustion head and air band adjutsments

Summary of Contents for 100CRD

Page 1: ...y stated other wise this manual must be used only by a qualified service technician Failure to comply with this or other requirements in this manual could result in severe personal injury death or sub...

Page 2: ...w Train the user To properly operate the burner appliance per this manual and the appliance instructions see User s information To keep this manual at or near the burner appliance for ready ac cess by...

Page 3: ...ctions when appliance data is not available Table 1 Apply the guidelines below to select a nozzle when appliance specific nozzle data is not avialable from the manufacturer See notes at end of table f...

Page 4: ...uvers screens Air opening sizes are always given in free area This means after deduction for louver obstruction If you can t find the louver reduction for the grilles used assume free area is 20 of to...

Page 5: ...ponents maintain all necessary clearances to combustible construction including the correct design of thimbles and insulation where penetrating combustible walls Illustrations A to F in Figure 1 show...

Page 6: ...surfaces dry base design E Chamber with refractory floor and water backed target wall without target refractory lining F Chamber with refractory floor and water backed target wall with target refrac t...

Page 7: ...spirit level Adjust flange if needed 7 The end of the air tube should be flush or almost flush with the inside of the combustion chamber wall 8 Verify the air tube is level and inserted the correct d...

Page 8: ...sertionmethods are intended only for negative overfire pressure For pressur ized firing you must obtain a burner with a welded flange designed for use with the specific appliance Failure to comply cou...

Page 9: ...from escaping from the housing Replace the gasket if not in good condition 9 Inspect the ignitor contact clips Clean or replace if necessary to ensure reliable contact with the electrodes Install noz...

Page 10: ...tely inserted into the housing collar and the Set initial burner air settings Combustion head 1 The combustion head adjusting slide controls the spacing between the retention ring and throttle ring or...

Page 11: ...02CRD oil burners Instruction manual Carlin part number MN99102 Rev 08 20 08 11 3 Prepare burner continued Figure 13 Combustion head air tube combinations typical Table 3 Approximate air band and comb...

Page 12: ...ctly sized and installed and that the fuel flow is unob structed the oil tank is clean and only 1 or 2 heating oil are supplied Failure to supply a reliable oil flow could result in loss of heat and p...

Page 13: ...bustion ventilation air openings and vent system Fuel supply line in good condition and sized designed correctly Oil tank has oil and oil line valves are open Wiring installed per burner appliance ins...

Page 14: ...r 5 Make sure the burner and appliance are correctly wired and the line switch is properly fused for the load To start burner Do not start the burner if the combustion chamber contains oil or oil vapo...

Page 15: ...Model 99FRD 100CRD 102CRD oil burners Instruction manual Carlin part number MN99102 Rev 08 20 08 15...

Page 16: ...the burner 5 Make sure the burner and appliance are correctly wired and the line switch is properly fused for the load To start burner Do not start the burner if the combustion chamber contains oil or...

Page 17: ...Model 99FRD 100CRD 102CRD oil burners Instruction manual Carlin part number MN99102 Rev 08 20 08 17...

Page 18: ...or use with security fire alarm systems such as Carlin SecureHeat 6 Make sure the burner and appliance are correctly wired and the line switch is properly fused for the load To start burner Do not sta...

Page 19: ...Model 99FRD 100CRD 102CRD oil burners Instruction manual Carlin part number MN99102 Rev 08 20 08 19...

Page 20: ...als Operate all zones and verify that there is never a voltage reading at the meter A voltage reading indicates incorrect wiring that must be corrected before attempting to operate the burner 5 Alarm...

Page 21: ...Model 99FRD 100CRD 102CRD oil burners Instruction manual Carlin part number MN99102 Rev 08 20 08 21...

Page 22: ...with instruments a Check smoke It should be zero on the Bacharach scale b Set the appliance flue damper or barometric draft regulator so the draft or pressure in the vent complies with the appliance...

Page 23: ...the appliance manual with the user Verify the user is aware of all procedures specified in the manuals Verify user will not store or use combustible liquids or materials or contaminants in the vicinit...

Page 24: ...ting 22996S 11 C Air tube combustion head combination 21915 Two stage Suntec B2VA 8216 w fitting 23002S 13 Air tubes Single stage Danfoss BFPH w fitting 27813D 5 nominal approx 5 3 8 oal 44990 Single...

Page 25: ...Model 99FRD 100CRD 102CRD oil burners Instruction manual Carlin part number MN99102 Rev 08 20 08 25 7 Repair parts continued...

Page 26: ...rer s recommendations Any time you replace a component or disassemble any part of the burner for service maintenance perform a complete operational test after reassembly to verify the burner operates...

Page 27: ...EZ Pro Burners that fall within the extended warranty period such defective parts should be returned freight prepaid to Carlin The repaired component or replacement part will be provided to the Custo...

Page 28: ...at all Never attempt to use gasoline as a fuel for this burner as it is more combustible and could result in a serious explosion Never attempt to burn refuse or use any fuel other than 1 or 2 heating...

Reviews: