background image

Model 301GAS burner — Instruction manual

Carlin part number MN301GAS Rev. 11/24/14

– 10 –

Where appliance instructions differ from this manual, follow the appliance instructions.

2.  Install gas piping from meter to combination gas train

Code compliance

The burner/appliance installation must comply with codes listed on page 2 

and any other locally applicable codes.

Piping from gas meter to burner

  Connect from the gas supply to the burner gas train inlet using 

new, clean black iron pipe and malleable iron fittings only. Do 

not use copper, brass, cast iron or galvanized pipe or fittings. 

 

Provide support for gas piping. Do not rest the weight of the 

gas piping on burner gas train.

 

Provide a support for the burner gas train.

 

Apply pipe dope sparingly at all joints. Use only pipe dope listed 

for use with propane gas. Do not use pipe sealing tape.

 

Do not hold the gas valve with pipe wrench. Use crescent 

wrench or other smooth-jawed device. Do not overtighten. 

 

Failure to comply with above could result in severe personal 

injury, death or substantial property damage.

1.  If possible, install a new gas line directly from the gas meter. If you are 

using an existing gas line, verify it is clean and in good condition, and 

verify it is large enough to handle the load of all connected appliances.

2.  When branching from a common gas line, do not tap off from the bottom 

of horizontal sections — only from the side or top.

3.  Install a main manual shutoff valve, sediment trap and ground joint union 

near the burner combination gas valve connection as shown in Figure 10.

4.  If the burner is installed inside an appliance jacket, install the main manual 

gas valve and sediment trap external to the jacket.

5.  Size piping (or verify size) using Table 2. You will find additional information 

on gas line sizing in the National Fuel Gas Code, NFPA 54/ANSI Z223.1, 

or B149.1/B149.2 Installation Code for Canadian Installations.

Gas supply pressure — 

natural or propane

•  Maximum supply pressure: 14 inches w.c.
•  Minimum supply pressure:   5 inches w.c.

  Do not expose the gas train to gas pressure in excess of 14 

inches water column. Higher pressure could damage the valve 

seat, resulting in potentially hazardous condition. When pres-

sure testing piping at higher pressures, disconnect burner from 

gas line before testing.

 

If the gas supply pressure can exceed 14 inches water col-

umn at any time, you must install a lockup type gas pressure 

regulator in the gas supply piping, ahead of the main manual 

gas valve installed at the burner.

Test and purge gas line

Read WARNING above.
Pressure test and purge the line. Pressure testing should be done by the gas 

supplier or utility, following all applicable codes.

1  Pipe to meter or branch
2  T-handle main manual gas valve
3  Use clean, burr-free black iron pipe 

and malleable iron fittings

4  Ground joint union

Figure 10

 

Connecting gas supply piping to burner

Table 2

 

Capacities of black iron pipe, cubic feet gas/

hour

5  Sediment leg
6  Upstream pressure tap, 1/4”
7  Outlet pressure tap, 1/4”
8  Gas regulator access screw
9  Gas valve wire junction box

NATURAL GAS

Capacities in 

Cubic feet per hour 

for Schedule 40 metal pipe 

Pipe size

 

(inches)

Total length of gas piping, 

from meter to burner connection (feet)

20

40

60

80

100

Natural gas @ .60 specific gravity, pressure drop 0.3 in. w.c.

 (note 1)

730

500

400

350

305

1,100

760

610

530

460

2

2,100

1,450

1,150

990

870

3,300

2,300

1,850

1,600

1,400

Natural gas @ .60 specific gravity, pressure drop 0.5 in. w.c.

 (note 1)

1

465

320

260

220

195

950

660

530

460

400

1,460

990

810

690

620

2

2,750

1,900

1,520

1,300

1,150

4,350

3,000

2,400

2,050

1,850

Note 1

For natural gas with specific gravity other than 0.60, consult 

National Fuel Gas Code, NFPA 54/ANSI Z223.1, or Canadian 

B149.1/B149.2 for correction factor.

PROPANE GAS

Capacities in 

Btuh

 for 

Schedule 40 metal pipe

Propane gas @ 1.5 specific gravity, pressure drop 1 psi

½

1,684

1,157

929

795

705

¾

3,521

2,420

1,943

1,663

1,474

1

6,632

4.558

3,660

3,133

2,776

Propane gas @ 1.5 specific gravity, pressure drop 0.5 in. w.c.

1

735

506

411

348

308

1502

1043

838

727

632

2308

1565

1281

1091

980

Summary of Contents for 301GAS

Page 1: ...el 60200FR microprocessor control Agencies UL Listed Installer servicer Except where specifically stated other wise this manual must be used only by a qualified service technician In the state of Mass...

Page 2: ...nually for start up and burner appliance service When servicing the burner Disconnect electrical supply to burner before attempting to service to avoid electrical shock or possible injury from moving...

Page 3: ...ge omitted for clarity with powder coat paint finish 15 Flame rod insulator assembly 16 Combustion head 17 Gas saddle connection gasket 18 Gas manifold 19 Ignition electrode insulator assembly 20 Stat...

Page 4: ...chimney that has one or more sides exposed to the outside Install a listed stainless steel liner to vent the flue products A defective vent system could result in severe personal injury death or subst...

Page 5: ...iance instruction manual when available to size combustion air openings Use the following guidelines when appliance instructions are not available All air from inside building building must be well ve...

Page 6: ...amic fiber or Fiberglass insulation Ceramic fiber materials such as chamber liners may contain carcinogenic particles chrystobalites after exposure to heat Airborne particles from fiberglass or cerami...

Page 7: ...ner does not comply with the specifications of Table 1 and other guidelines in this manual Combustion head air tube configurations 301GAS burners are supplied with either an B or C head and air tube c...

Page 8: ...g b Close the manual gas valve on the gas supply line c Disconnect the burner gas train union d Remove the gas pipe at the burner air tube e Remove the four nuts securing the burner hinged door flange...

Page 9: ...x a Match wire colors of the incoming wires to those pre wired to the terminal strip inside the gas train J box b See the label in the burner junction box or the wiring diagram on page 11 Gas valve ve...

Page 10: ...supply pressure 14 inches w c Minimum supply pressure 5 inches w c Do not expose the gas train to gas pressure in excess of 14 inches water column Higher pressure could damage the valve seat resultin...

Page 11: ...hite wires are from the 120 vac HOT side and that the power is no less than 102 vac nor more than 132 vac Checking burner flame signal The 60200FR uses flame rectification to detect the flame Because...

Page 12: ...oap suds mixture to all gas piping joints near burner and check for any leaks If any leaks appear repair before proceeding Figure 12 Air band adjustment and retest Set burner air band See Figure 12 Lo...

Page 13: ...e control will restart Releasing the button before the LED s turn off will cause the control to remain in latch up The 60200FR control will not reset from lockout or latch up if power is interrupted P...

Page 14: ...firing rate Preparation before checkout Burner appliance installed per appliance instruction manual Burner components verified against Table 1 page 7 Burner appliance installed per all applicable cod...

Page 15: ...pressure switch to a pressure less than actual manifold pressure The high gas pressure switch should shut the burner down Replace the switch if necessary Turn off power to the appliance burner remove...

Page 16: ...ng studs Perform the complete checkout procedures of pages 12 through 15 including system inspection and checks 6 Maintenance and service procedures Maintenance service procedures Cleaning blower whee...

Page 17: ...Model 301GAS burner Instruction manual Carlin part number MN301GAS Rev 11 24 14 17 Where appliance instructions differ from this manual follow the appliance instructions 7 Troubleshooting...

Page 18: ...mary voltage to ignitor If ignitor receives 120 VAC and doesn t generate spark replace ignitor Airflow Check air band setting against Table 1 page 7 Wrong orifice size Verify orifice size per Table 1...

Page 19: ...flange burner verify the insertion depth on the appliance and burner see page 7 If using the adjustable flange Figure 14 measure the appliance inser tion depth to the set the position of the flange on...

Page 20: ...augmenter NA 5 Air band four slot 47001S 6 Air shutter low input range B head tube Air shutter mid input range C head tube 99254 99278 7 Blower wheel 5 diameter x 4 deep 28563S 8 Motor Carlin PSC 1 6...

Page 21: ...al follow the appliance instructions 9 Replacement parts Burner continued 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Set screws Burnerisshownwithweldedflange suppliedonlyonburners ordered for specif...

Page 22: ...box 99517 7 Primary gas valve Honeywell V48A 1 NPT Bleed restrictor fixed 99227 99228 8 Pipe nipple schedule 40 steel 1 NPT x 4 long Obtain locally 9 Pipe nipple schedule 40 steel 1 NPT x 2 long Obta...

Page 23: ...301GAS burner Instruction manual Carlin part number MN301GAS Rev 11 24 14 23 Where appliance instructions differ from this manual follow the appliance instructions 9 Replacement parts Gas train conti...

Page 24: ...Model 301GAS burner Instruction manual Carlin part number MN301GAS Rev 11 24 14 24 Where appliance instructions differ from this manual follow the appliance instructions...

Reviews: