background image

Model 301GAS burner — Instruction manual

Carlin part number MN301GAS Rev. 11/24/14

– 9 –

Where appliance instructions differ from this manual, follow the appliance instructions.

Mount burner in appliance

•  Verify appliance burner front plate dimensions and bolt locations.

•  Slide gasket supplied with burner over end of air tube.
•  Insert burner into appliance opening and bolt in place.
•  Level the housing if necessary by loosening the set screws securing the 

housing to the air tube. Retighten the set screws.

Inspect components and wiring

•  Visually inspect all burner components and wiring.
•  Verify that wiring is intact and leads are securely connected.
•  Verify that all burner components are in good condition.
•  Check gas pressure switch settings. Set the low gas pressure switch at 

manifold setting minus 50%.  Set the high gas pressure switch at manifold 

setting plus 50%.

Figure 8

 

Gas orifice location

Install gas train on burner

1.  The standard burner gas train is shipped fully assembled, with the piping 

disconnected at the gas train union. See separate instructions if installing 

an optional knocked down gas train.

2.  Connect the gas train at the union (Figure 9).

  To avoid damage to gas train components, do not hold compo-

nents with a pipe wrench or overtighten. Use only a crescent 

wrench or other means. Failure to comply could result in severe 

personal injury, death or substantial property damage.

3.  Connect the flexible conduit, pre-attached to the primary control J-box, 

to the gas train J-box, and attach the wires to the terminal strip inside 

the gas train J-box.

a.  Match wire colors of the incoming wires to those pre-wired to the terminal 

strip inside the gas train J-box.

b.  See the label in the burner junction box or the wiring diagram on page 11.

  Gas valve vent opening — If local codes require, install pip-

ing from vent connection to outside, sized and installed as 

required by codes. A vent limiting orifice is provided. Install in 

vent opening, if starts are hard, before piping to outside.

Figure 9

 

Gas train installation

Inspect/redrill gas orifice

  If the burner is installed, you must disconnect power to burner 

and close main manual gas valve before proceeding. Failure to 

do so could result in severe personal injury, death or substantial 

property damage.

  In the state of Massachusetts, when lever-type gas shutoffs 

are used, they must be T-handle type only.

1.  Turn off power to the burner/appliance before proceeding.
2.  Close main manual gas valve in gas supply line to burner.
3.  Disconnect the burner gas train union if the burner/gas train is installed. 

See Figures 8 and 9.

4.  Locate the correct orifice drill size in Table 1, page 7 (or appliance 

manual). Then check actual orifice size using that size drill bit.

5.  If the gas orifice is smaller than required, unscrew the orifice nipple 

from the elbow. Then redrill the orifice to the correct size. Replace the 

gas train, using only pipe dope listed for use with liquefied petroleum 

gases.

6.  If the gas orifice is larger than required, remove the orifice nipple 

from the elbow. Obtain a replacement orifice nipple. If necessary, drill 

the correct orifice hole in the new orifice to the correct size.

7.  Replace gas train. Seal pipe joints with a small amount of pipe dope. 

Use only pipe dope approved for use with propane gas.

1.  Prepare site   •   prepare burner   •   mount burner 

(continued)

Summary of Contents for 301GAS

Page 1: ...el 60200FR microprocessor control Agencies UL Listed Installer servicer Except where specifically stated other wise this manual must be used only by a qualified service technician In the state of Mass...

Page 2: ...nually for start up and burner appliance service When servicing the burner Disconnect electrical supply to burner before attempting to service to avoid electrical shock or possible injury from moving...

Page 3: ...ge omitted for clarity with powder coat paint finish 15 Flame rod insulator assembly 16 Combustion head 17 Gas saddle connection gasket 18 Gas manifold 19 Ignition electrode insulator assembly 20 Stat...

Page 4: ...chimney that has one or more sides exposed to the outside Install a listed stainless steel liner to vent the flue products A defective vent system could result in severe personal injury death or subst...

Page 5: ...iance instruction manual when available to size combustion air openings Use the following guidelines when appliance instructions are not available All air from inside building building must be well ve...

Page 6: ...amic fiber or Fiberglass insulation Ceramic fiber materials such as chamber liners may contain carcinogenic particles chrystobalites after exposure to heat Airborne particles from fiberglass or cerami...

Page 7: ...ner does not comply with the specifications of Table 1 and other guidelines in this manual Combustion head air tube configurations 301GAS burners are supplied with either an B or C head and air tube c...

Page 8: ...g b Close the manual gas valve on the gas supply line c Disconnect the burner gas train union d Remove the gas pipe at the burner air tube e Remove the four nuts securing the burner hinged door flange...

Page 9: ...x a Match wire colors of the incoming wires to those pre wired to the terminal strip inside the gas train J box b See the label in the burner junction box or the wiring diagram on page 11 Gas valve ve...

Page 10: ...supply pressure 14 inches w c Minimum supply pressure 5 inches w c Do not expose the gas train to gas pressure in excess of 14 inches water column Higher pressure could damage the valve seat resultin...

Page 11: ...hite wires are from the 120 vac HOT side and that the power is no less than 102 vac nor more than 132 vac Checking burner flame signal The 60200FR uses flame rectification to detect the flame Because...

Page 12: ...oap suds mixture to all gas piping joints near burner and check for any leaks If any leaks appear repair before proceeding Figure 12 Air band adjustment and retest Set burner air band See Figure 12 Lo...

Page 13: ...e control will restart Releasing the button before the LED s turn off will cause the control to remain in latch up The 60200FR control will not reset from lockout or latch up if power is interrupted P...

Page 14: ...firing rate Preparation before checkout Burner appliance installed per appliance instruction manual Burner components verified against Table 1 page 7 Burner appliance installed per all applicable cod...

Page 15: ...pressure switch to a pressure less than actual manifold pressure The high gas pressure switch should shut the burner down Replace the switch if necessary Turn off power to the appliance burner remove...

Page 16: ...ng studs Perform the complete checkout procedures of pages 12 through 15 including system inspection and checks 6 Maintenance and service procedures Maintenance service procedures Cleaning blower whee...

Page 17: ...Model 301GAS burner Instruction manual Carlin part number MN301GAS Rev 11 24 14 17 Where appliance instructions differ from this manual follow the appliance instructions 7 Troubleshooting...

Page 18: ...mary voltage to ignitor If ignitor receives 120 VAC and doesn t generate spark replace ignitor Airflow Check air band setting against Table 1 page 7 Wrong orifice size Verify orifice size per Table 1...

Page 19: ...flange burner verify the insertion depth on the appliance and burner see page 7 If using the adjustable flange Figure 14 measure the appliance inser tion depth to the set the position of the flange on...

Page 20: ...augmenter NA 5 Air band four slot 47001S 6 Air shutter low input range B head tube Air shutter mid input range C head tube 99254 99278 7 Blower wheel 5 diameter x 4 deep 28563S 8 Motor Carlin PSC 1 6...

Page 21: ...al follow the appliance instructions 9 Replacement parts Burner continued 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Set screws Burnerisshownwithweldedflange suppliedonlyonburners ordered for specif...

Page 22: ...box 99517 7 Primary gas valve Honeywell V48A 1 NPT Bleed restrictor fixed 99227 99228 8 Pipe nipple schedule 40 steel 1 NPT x 4 long Obtain locally 9 Pipe nipple schedule 40 steel 1 NPT x 2 long Obta...

Page 23: ...301GAS burner Instruction manual Carlin part number MN301GAS Rev 11 24 14 23 Where appliance instructions differ from this manual follow the appliance instructions 9 Replacement parts Gas train conti...

Page 24: ...Model 301GAS burner Instruction manual Carlin part number MN301GAS Rev 11 24 14 24 Where appliance instructions differ from this manual follow the appliance instructions...

Reviews: