background image

Tech Support (800) 989-2275

www.carlincombustion.com

Model 50200 CAD Cell Oil 

Primary Control Data Sheet

•  Interrupted Duty Ignition
• Recycle on Flame Failure

 

•  Serviceman Reset Protection  

Latch-up after 3 consecutive lockouts

•  Diagnostic LEDs  

Status, lockout, flame

• 15-second, 30-second TFI
• Thermostat/Aquastat Compatible
• SMC Technology 
•  Pump Prime
• Alarm Contacts

Power input (from limit circuit)

120 VAC, 60 HZ, 9VA

Motor load

10 FLA / 60 LRA

Ignitor load

120 VAC, 60 HZ, 500 VA

Alarm contacts

24 V, AC/DC, 2A

Operating temperature limits

+32°F to +140°F

Storage temperature limits

-40°F to +185°F

Thermostat anticipator current

0.1 A, AC

CAD cell resistance (with flame)

R < 1500 OHMS

Agencies

UL recognized (US & Canada)

Installing and Wiring

  50200 control must be installed and serviced only by a qualified service technician.

1.   Always disconnect power source before wiring to avoid electrical shock or damage to the control. All wiring must comply with 

applicable codes and ordinances.

2.   Thermostat terminals (T-T) provide a current source. Never apply external power to these terminals under any circumstances.
3.    Alarm terminals provide a 24 VAC/VDC-rated dry contact, suitable for use with security/fire alarm systems.

Mounting
•  The control may be mounted on a 4" x 4" junction box in any convenient location on the burner, furnace or wall. The location 

must not exceed the ambient temperature limit, 140°F.

Wiring
• Wiring must comply with local and national electrical codes, and with the wiring diagram.
• Individual or bundled neutrals may be attached to any L2 terminal.

Field checks
1. 

 Safety timing (TFI) test – Remove one CAD cell wire (F-F). Start burner. The control should lockout within the TFI time limit. 

Replace CAD cell wire.

2.  

Flame failure test – Start burner. After flame is established (after TFI period), close the oil supply hand valve. This will cause a 

flame failure sequence as described in the Startup & Operation section of this Data sheet. The control should recycle (restart 

after 65 seconds).

3.  If control does not operate as described, check the wiring.

SEE WIRING DIAGRAM ON NEXT PAGE

Summary of Contents for 50200

Page 1: ...th applicable codes and ordinances 2 Thermostat terminals T T provide a current source Never apply external power to these terminals under any circumstances 3 Alarm terminals provide a 24 VAC VDC rated dry contact suitable for use with security fire alarm systems Mounting The control may be mounted on a 4 x 4 junction box in any convenient location on the burner furnace or wall The location must n...

Page 2: ...is successful amber LED turns off and control waits for thermostat circuit to close and a limit input Call for Set thermostat to call for heat Thermostat circuit must be closed and black wire must receive heat power from the limit circuit Self test 2 If a failure occurs in this self check the control won t start and the amber LED blinks 1 second on 4 sec onds off until serviced or the problem clea...

Page 3: ...d closes the alarm contact To Reset Push in and hold reset button for 1 second then release Latch up If the control locks out 3 times during a single call for heat latch up occurs The control turns on both the amber and red LEDs constant You must use the special procedure below to reset the control after latch up Reset after latch up only a qualified service technician should attempt to reset the ...

Page 4: ...sing Check for stray light by measuring the CAD cell resistance looking into the inactive combustion chamber It should read at least 50 kohms Repeated flame failures flashing red LED Check for CAD cell is defective Replace Air leaking into oil line causing flame out Check oil line connections and filter gasket Defective nozzle causing flame to be erratic Change nozzle Excessive airflow or draft ca...

Reviews: