background image

© Copyright 2015 - Carlin Combustion Technology, Inc.  

MN50200  022415

Service & Troubleshooting

Burner (control) will not come on

  No power to control

 

•  Check limit circuit to the control (at least 102 VAC).

 

• Check all electrical connections.

  Control is in lockout

 

•  Red LED will be on. Press the reset button for 1 sec-

ond.

 

•  If the control returns immediately to lockout, the 

Safety Monitoring Circuit may have detected an 

internal control problem. Replace the control.

  CAD cell seeing light

 

•  Green LED on, and amber LED blinking 1 second 

on, 4 seconds off. Remove one yellow lead from FF 

terminals, and the flame test plug. 

 

 If the amber LED remains flashing and green LED on, 

the control is defective.

 

 If the amber and green LEDs go OFF, the control is 

OK, and;

 

• light is leaking into the burner housing, or

 

• CAD cell is defective, or

 

•  There is a problem with the CAD cell wiring or 

holder.

 

•  If appliance was recently shut down, CAD cell may 

see residual hot spots in chamber.

 

To troubleshoot:

 

•  Attach multimeter to monitor CAD cell resistance.  

Dark resistance should be over 50K ohms, and 

room light resistance (control flipped open) should 

be at most 10K ohms. Replace cell if necessary or 

reinstall and close the burner housing.

 

•  Check for stray light by measuring the CAD cell 

resistance looking into the inactive combustion 

chamber. It should read at least 50 kohms.

Repeated flame failures ( 

 flashing red LED)

 

Check for: 

 

• CAD cell is defective. Replace.

 

•  Air leaking into oil line causing flame out.  

Check oil line connections and filter gasket.

 

•  Defective nozzle causing flame to be erratic. 

Change nozzle. 

 

•  Excessive airflow or draft causing flame to leave 

burner head.  

Check for proper air band setting and draft.

 

•  Excessive back pressure causing flame to be er-

ratic. Check appliance and flue for sooting/plugging.

Control locks out after TFI ( 

 red LED on)

 

Check for: 

 

• No oil to burner. Check oil supply, filters, lines.

 

•  Shorted electrodes. Inspect for cracked porcelain 

and replace as needed.

 

•  Poor spark. Check electrode spacing and condition 

per burner manual. Replace or realign if necessary.

 

• Nozzle clogged. Replace nozzle.

 

• Airflow too high. Check air band setting.

 

• Ignitor module defective. Replace if no spark.

 

• CAD cell defective

 

• Oil valve (if used) stuck in closed position.

 

• Check wiring connections.

 Blinking Green LED

 

• Weak or unstable flame.

 

• Check ohms.

 

• Check CO

2

 level.

   

FROZEN PIPES/WATER DAMAGE: This is not a freeze protection device. Suitable freeze protection monitoring or 

other precautions are recommended to protect against ruptured pipes/water damage caused by fuel outage, safety 

related fault conditions, or equipment failures.  

Summary of Contents for 50200

Page 1: ...th applicable codes and ordinances 2 Thermostat terminals T T provide a current source Never apply external power to these terminals under any circumstances 3 Alarm terminals provide a 24 VAC VDC rated dry contact suitable for use with security fire alarm systems Mounting The control may be mounted on a 4 x 4 junction box in any convenient location on the burner furnace or wall The location must n...

Page 2: ...is successful amber LED turns off and control waits for thermostat circuit to close and a limit input Call for Set thermostat to call for heat Thermostat circuit must be closed and black wire must receive heat power from the limit circuit Self test 2 If a failure occurs in this self check the control won t start and the amber LED blinks 1 second on 4 sec onds off until serviced or the problem clea...

Page 3: ...d closes the alarm contact To Reset Push in and hold reset button for 1 second then release Latch up If the control locks out 3 times during a single call for heat latch up occurs The control turns on both the amber and red LEDs constant You must use the special procedure below to reset the control after latch up Reset after latch up only a qualified service technician should attempt to reset the ...

Page 4: ...sing Check for stray light by measuring the CAD cell resistance looking into the inactive combustion chamber It should read at least 50 kohms Repeated flame failures flashing red LED Check for CAD cell is defective Replace Air leaking into oil line causing flame out Check oil line connections and filter gasket Defective nozzle causing flame to be erratic Change nozzle Excessive airflow or draft ca...

Reviews: