background image

with Sensor Redundancy

Data sheet

126 Bailey Road 

North Haven, CT 06473

Phone  203-680-9401 

Fax  203-680-9403

Carlin Combustion Technology

T

ech

 

support

  800-989-2275

carlincombustion.com

©

 

Copyright 2021 – Carlin Combustion Technology

Specifications

•  Carlin’s Model 90320 microprocessor-operated, multiple-contact tem-

perature limit controls are available as described below. The model 

provides two contacts — one for operating limit and one for high limit.

•  Refer to separate product listing sheets for pre-defined models, or re-

quest a control to meet your specifications, within the available ranges 

listed below.

90320

B

Dual limit temperature control

•  operating and high limit action

•  smart manual reset on high limit

•  operating limit sensors, redundant

•  high limit sensor

•  operating and limit contacts in series

Control model

B

Control power input

 (red-white wire)

240 

VAC

, 50/60 hz, 12 

VA

Contacts

2 in series

Contact rating

Motor load
General

240 

VAC

, 50/60 hz, 1 

HP

120/240 

VAC

, 50/60 hz, 15 

AMPS

Wires

Quantity

3

240 

VAC

 Hot  /  Neutral

red-white / white

Limits OUT

black

Adjustable oper. limit range

Any range between 50°F to 240°F

Fixed high limit temperature

Any value from 160°F to 240°F

Fixed differential (subtractive)

Any value from 5°F to 100°F

Operating temperature limits

+32°F  to  +140°F

Storage temperature limits

–40°F  to  +185°F

Agencies

m

  Multiple sensor option (3) 

(Using individual and/or dual sensor assemblies)

m

  Sensor Redundancy 

(Higher temperature of two operating sensors used)

m

  Easy remote sense 

(Electronic sensors, wired to control)

m

  Smart manual reset 

(Manual reset only if operating limit doesn’t open)

m

  Serviceman reset protection 

(Latch-up after three consecutive lockouts 

(1)

)

m

  Power-independent lockout 

(Power cycling won’t reset from lockout or latch-up)

m

  Diagnostic LED’s 

(Call for heat, and lockout/latchup)

m

  

SMC

 Technology

 

(2)

(1)  Latch-up mode shuts down the control after three consecutive lockouts, and requires a 

special procedure to reset. This ensures the owner will call in a licensed technician to 
troubleshoot and correct burner problems.

(2)  The 90320 provides two limit relays. Carlin’s patented SMC technology (Safety Monitoring 

Circuit) monitors the contacts of both relays. 

Lockout 

occurs if a limit relay contact is found 

closed when it should be open.

Reviews: