Model 90320 Microprocessor Temperature Controls — Data sheet

Mounting – 

90320 controls mount to any standard well. Mount the 

90320 directly to a well (new or existing) with hardware sup-

plied in the separate well mounting kit.  

Well Kits – 

Wells for 90320 sensors are available in the sizes shown 

below. Well kits include sensor mounting hardware designed to 

hold sensor securely in position. 

Sensors – 

Sensors are available separately for the 90320. 

Configurations

3"

4

3

/

8

"

4

3

/

4

"

Error Codes

Error Code

Reason

01

Primary (K2) relay is welded on. 

Note: 

If the control is reset 

from error code 01, the red LED will flash every 5 seconds 

indicating the control must be replaced.

02

Primary & Safety relays (K1 and K2) on. The control cannot 

be reset from error code 02 and must be replaced.

03

Primary & Safety relays (K1 and K2) are off. 

Note:

 If this 

error is detected, the control will show error code 

03

 and 

enter soft lockout two times to try and resolve the issue. If 

the problem persists the control will enter hard lockout.

05

Simulated High Temp lockout. Push the RESET button.

06

Temp is above set high temp but below thermistor high 

(250°F). This is a common occurrence once the burner 

turns off.

Error Code

Reason

20

Temp sensor 1 out of range failure. Replace sensor 1.

21

Temp sensor 2 out of range failure. Push the RESET button.

22

High limit temp sensor out of range failure. Replace the 

high temp sensor.

23

Temp sensor 1 pin is open. Replace sensor 1.

24

Temp sensor 2 pin is open. Replace sensor 2.

25

High limit temp sensor is open. Replace the high temp 

sensor.

10

,

  1 1

,

 12

,

 13

,

 14

,

 15

Internal hardware safety failure – unit should be replaced. Contact customer service for additional informa-

tion. 1-800-989-2275