9
EM24 IS use
EM24 IS - Instruction manual | CARLO GAVAZZI Controls SpA
EM24 IS - Instruction manual | CARLO GAVAZZI Controls SpA
Menu description
Measurement menu - measurement pages
The displayed pages depend on the application set and digital input settings.
Page
Displayed measurements
Description
1
L1-L2-L3
V
LNΣ
Hz
Phase sequence
System phase-neutral voltage
Frequency
2
L1-L2-L3
V
LLΣ
Hz
Phase sequence
System phase-phase voltage
Frequency
3
Tot kWh (+)
W
Σ
dmd
W
Σ
dmd max
Total imported active energy
System active power dmd
System active power dmd max
4
kWh
A dmd max
PArt
Partial imported active energy
Maximum dmd current
5
Tot kvarh (+)
VA
Σ
dmd
VA
Σ
dmd max
Total imported reactive energy
System apparent power dmd
System apparent power dmd max
6
kvarh
VA
Σ
PArt
Partial imported reactive energy
System apparent power
7*
Totalizer 1
(
tAr, GAS, m3 Cold, m3 Hot,
kWh tot, kWh out, rEM, SYnC)
multi-tariff management, gas metering, cold water metering, hot water metering, distant heating
(kWh) meters, reading of an external energy counter, for reading the digital input status by means
of serial communication, dmd calculation synchronisation
Pulse input 1
8*
Totalizer 2
(
tAr, GAS, m3 Cold, m3 Hot,
kWh tot, kWh out, rEM, SYnC)
multi-tariff management, gas metering, cold water metering, hot water metering, distant heating
(kWh) meters, reading of an external energy counter, for reading the digital input status by means
of serial communication, dmd calculation synchronisation
Pulse input 2
9*
Totalizer 3
(
GAS, m3 Cold, m3 Hot, kWh
tot, kWh out, rEM, Sync)
gas metering, cold water metering, hot water metering, distant heating (kWh) meters, reading of
an external energy counter, for reading the digital input status by means of serial communication
Pulse input 3
10*
kWh (+)
t1
W
Σ
dmd
Imported active energy, tariff 1
System active power dmd
11*
kWh (+)
t2
W
Σ
dmd
Imported active energy, tariff 2
System active power dmd
12*
kWh (+)
t3
W
Σ
dmd
Imported active energy, tariff 3
System active power dmd
13*
kWh (+)
t4
W
Σ
dmd
Imported active energy, tariff 4
System active power dmd
14*
kvarh (+)
t1
W
Σ
dmd
Imported reactive energy, tariff 1
W
Σ
dmd
15*
kvarh (+)
t2
W
Σ
dmd
Imported reactive energy, tariff 2
W
Σ
dmd
16*
kvarh (+)
t3
W
Σ
dmd
Imported reactive energy, tariff 3
W
Σ
dmd
17*
kvarh (+)
t4
W
Σ
dmd
Imported reactive energy, tariff 4
W
Σ
dmd
18
kWh (+) X
W X
User X
Imported active energy
Active power
User
19
kWh (+) Y
W Y
User Y
Imported active energy
Active power
User
Summary of Contents for EM24 IS-R2-O2 Series
Page 2: ...EM24 IS R2 O2 XX Three phase energy analyzer USER MANUAL...
Page 21: ...EM24 IS R2 O2 XX Analizzatore di energia per sistemi trifase MANUALE UTENTE...
Page 40: ...EM24 IS R2 O2 XX Dreiphasen Energieanalysator BETRIEBSANLEITUNG...
Page 59: ...EM24 IS R2 O2 XX Analyseur d nergie triphas MANUEL D EMPLOI...
Page 78: ...EM24 IS R2 O2 XX Analizador de energ a trif sico INSTRUCCIONES DE USO...
Page 97: ...EM24 IS R2 O2 XX Trefaset energianalyseapparat BRUGERMANUAL...