9
EM24 W1 use
EM24 W1 - Instruction manual | CARLO GAVAZZI Controls SpA
EM24 W1 - Instruction manual | CARLO GAVAZZI Controls SpA
Wireless M-Bus communication setting
Setting wireless M-Bus parameters
Step
Action
Button
1
Press the button for at least 3 seconds
2
In the
PASS?
page, select the correct password (default 0)
3
Confirm operation
4
Scroll pages until
ModE
5
Press the joystick to edit the parameter
6
Select the option
7
Confirm
8
Go to
FrAME
9
Press the button to edit the parameter
10
Select the frame type according to the desired variables:
Variable
Frame 1
Frame 2
Frame 3
Frame 4
Total imported active
energy
●
●
●
●
Total exported active
energy
●
Total imported reactive
energy
●
●
●
Total exported reactive
energy
●
●
●
Imported active power
●
●
●
Exported active power
●
Imported reactive power
●
●
Exported reactive power
●
●
Current L1
●
Current L2
●
Current L3
●
Voltage L1-N
●
Voltage L2-N
●
Voltage L3-N
●
Supply frequency
●
Error flag
●
●
●
●
12
Confirm
13
Scroll pages until
interVAL