4.3
Start-up Parameters
The list of start-up parameters includes the parameters for all possible 32 devices that can be connected to 1
NRGC-EIP controller. You can identify the address of the End device by the End Device XX where xx indicates the
position of the device on the bus chain. All start-up parameters are associated with the exclusive owner
connection.
If there are less than 32 devices e.g. 18 devices on the bus chain, the remaining settings for End device 19 up to End
device 32 can be ignored.
Parameter
Description
Values
End Device XX
Device type
Set the part number of the
device connected on the bus
chain.
Select ‘Emp
t
y’ if no device is
connected on that slot.
Empty/
RGC1A60CM25KEN/
RGC1A60CM32KEN/
RGC1A60CM32GEN/
RGC1A60CM42GEN/
RGC1A60CM62GEN/
RGS1A60CM50KEN/
RGS1A60CM92KEN/
RGS1A60CM92GEN/
(for future use)
RGC1P60CM25KEN/
RGC1P60CM32KEN/
RGC1P60CM32GEN/
RGC1P60CM42GEN/
RGC1P60CM62GEN/
RGS1P60CM50KEN/
RGS1P60CM92KEN/
RGS1P60CM92GEN
Voltage compensation
Reserved for future use
Switching mode
Set the switching mode that the
RG..N shall use at the output
External /
ON/OFF (default) /
Burst /
Advanced full cycle
/
Distributed full
cycle/
Phase Angle
(
for future use
)
Timebase
Set the desired timebase. (only
applicable for Burst firing mode)
This parameter is in steps of 0.1,
therefore a value of 11 = 1.1s
0.1
- 10s
0.1s (default)
Substitute output mode
Set the output mode to be used
in case of a communication
timeout
Clear output /
Hold output
(default) /
Set Value
Substitute output value
Set the % control level to be
used in case of a
communication timeout. (Only
applicable for ‘Set Value option’
for Output substitute mode
0
–
100%
Default (0%)
Soft start ramping time
Reserved for future use
Soft start current limit mode
Reserved for future use
OFF time to soft start
Reserved for future use