15
V1.0 | NRG EtherNet/IP Preliminary User Manual | © 2020 | CARLO GAVAZZI LTD.
EN
The list of start-up parameters can be sorted out by end device number from the
Group
drop down menu as shown
below.
4.4
EtherNet/IP factory reset
The NRGC-EIP shall accept two types of reset types:
Power Cycle
(Reset Type 0)
–
This will emulate as closely as possible to a power cycle of the device. This is the
default value if this parameter is omitted.
Return to Factory Defaults
(Reset Type 1)
–
This reset mode will return as closely as possible to the factory default
configuration, and then emulate power cycle as closely as possible of the device.
Apart from the standard reset functionality as specified in EtherNet/IP, Reset Type 1 shall set the auto-addressing
flag in the NRGC-EIP. Therefore, an auto-addressing command will occur on next NRGC-EIP powerup. For more
information regarding Auto-addressing function refer to Section 3.3
Note
Any of the above factory resets shall NOT perform a factory reset on the NRG solid state relays (RG..Ns). A
factory reset on the RG..Ns can be done via an explicit command. Refer to the Communications section for more
information.