V1.0 | NRG EtherNet/IP Preliminary User Manual | © 2020 | CARLO GAVAZZI LTD.
EN
NRG solid state relays
The RG..N solid state relays are the switching components in the NRG system.
They are available with and without heatsink. For a reference of the variants
available refer to the RG..N datasheet. The RG..CM..N utilises the
communication system for switching, measurement and diagnostic thus
minimising the number of components required in the system.
Through the internal BUS, the main controller can read measurement
parameters and diagnostics information related to the RG..N and its load.
The RG..N is also capable of detecting certain fault conditions. A fault
condition is indicated through a red LED available on the façade of the
RG..N. The type of fault can be identified through a specific flash rate of the
red LED and identified via the communication system.
Since the main controller needs to address each specific RG..N individually, each RG..N needs to be uniquely
identifiable. It is not required to physically set the ID for each RG..N. This can be done through an auto-addressing
function which occurs automatically on the first start up; whereby each RG..N on the bus chain will automatically be
assigned an ID with respect to its physical placement on the internal bus.
NRG internal cables
The RCRGN-xxx-2 is a 5-way proprietary cable used for the internal BUS, i.e., between the NRG
controller and the first RG..N on the BUS chain and between respective RG..Ns on the BUS. This
internal BUS cable though terminated with a micro-USB plug is not a standard USB cable.
Apart from the data and supply lines, the RCRGN-xxx-2 are equipped with an additional wire
utilised for the auto-addressing of the RG..Ns on the NRG bus chain. These cables are
available in various lengths from Carlo Gavazzi.
For further technical information on each NRG system component please refer to the respective product datasheets:
System
component
Datasheet
QR Codes
NRGC-EIP
https://gavazziautomation.com/images/PIM/DATASHEET/ENG/SSR_NRGC_EIP.pdf
NRGC-PN
http://gavazziautomation.com/docs/mt_gh/SSR_NRGC_PN.pdf
RG..CM..N
/
RCRGN-
xxx-2