Specifications are subject to change without notice (14.04.2010)

RGC

Note:

Control input lines must be installed together to maintain products' susceptability to Radio Frequency interference.Use of AC solid state relays may,
according to the application and the load current, cause conducted radio interferences. Use of mains filters may be necessary for cases where the user must
meet E.M.C requirements. The capacitor values given inside the filtering specification tables should be taken only as indications, the filter attenuation will
depend on the final application. DC input type require surge suppression for full compliance to EN55011.

Performance Criteria 1:

No degradation of performance or loss of function is allowed when the product is operated as intended.

Performance Criteria 2:

During the test, degradation of performance or partial loss of function is allowed. However when the test is complete the

product should return operating as intended by itself.

Performance Criteria 3:

Temporary loss of function is allowed, provided the function can be restored by manual operation of the controls.

Conformance

IEC/EN 62314
IEC/EN 60947-4-2
IEC/EN 60947-4-3

EMC Immunity

IEC/EN 61000-6-4

EMC Emission

IEC/EN 61000-6-2

Electrostatic Discharge (ESD)
Immunity

IEC/EN 61000-4-2

Air discharge

8kV, Performance Criteria 2

Contact

4kV, Performance Criteria 2

Electrical Fast Transient
Burst Immunity

IEC/EN 61000-4-4

Output

2kV, Performance Criteria 1

Input

1kV, Performance Criteria 1

Electrical Surge Immunity

IEC/EN 61000-4-5

Output, line to line

1kV, Performance Criteria 1

Output, line to earth

2kV, Performance Criteria 1

Input, line to line

1kV, Performance Criteria 2

Input, line to earth

2kV, Performance Criteria 2

Radio Interference
voltage emission (conducted)

IEC/EN 55011

0.15 - 30MHz

Class A (industrial)
- see filter information
IEC/EN 60747-4-X
Class A (no filtering needed)

Agency Approvals

UL508 LISTED (E172877),
VDE (pending), CUL

Radiated Radio Frequency
Immunity

IEC/EN 61000-4-3

10V/m, 80 - 1000 Mhz

Performance Criteria 1

10V/m, 1.4 - 2.0GHz

Performance Criteria 1

1V/m, 2.0 - 2.7GHz

Performance Criteria 1

Conducted Radio Frequency
Immunity

IEC/EN 61000-4-6

10V/m, 0.15 - 80 MHz

Performance criteria 1

Voltage Dips Immunity

IEC/EN 61000-4-11

0% for 10ms/20ms,

70% for 500ms

Performance Criteria 2

40% for 200ms

Performance Criteria 2

Voltage Interruptions Immunity

IEC/EN 61000-4-11

0% for 5000ms

Performance Criteria 2

Radio Interference
voltage emission (conducted)

IEC/EN 55011

0.15 - 30MHz

Class A (industrial)
- see filter information

Agency Approvals and Electromagnetic Compatibility

Filtering - EN / IEC 55011 Class A compliance

(for class B compliance contact us)

Part Number

Suggested filter for compliance

Maximum Heater current

RGC1A23D20KKE

68 nF / 275 V / X1

20A

RGC1A23A20KKE

220 nF / 275 V / X1

30A

RGC1A60D20KKE

100 nF / 1000 V / X1

20A

RGC1A60A20KKE

330 nF / 1000 V / X1

30A

Summary of Contents for RGC1A

Page 1: ...m design incorporating product ratings at a surrounding temperature of 40 C The smallest width is 17 5mm and is rated at 20 AAC Power and control teminals allow for safe looping of cables Voltage transient protection is standard across the output with a varistor Specifications are stated at 25 C unless otherwise noted Solid State Relays Zero Switching Types RGC Solid State Contactor E Contactor Co...

Page 2: ...e category III fixed installations General Specifications Isolation Input to Output 4000Vrms Input Output to Case 4000Vrms AC input current Vs Input Voltage DC input current Vs Input Voltage RGS D 1 RGS A Control voltage range RGC 23 3 32 VDC 20 275 VAC 24 10 190 VDC RGC 60 4 32 VDC 20 280 VAC 24 10 190 VDC Pick up voltage RGC 23 3 0 VDC 20 VAC DC RGC 60 3 8 VDC Drop out voltage RGC 23 1 2 VDC 5 V...

Page 3: ...C 30 Rated operational current AC 51 rating Ta 40 C 20 AAC 30 AAC AC 53a rating Ta 40 C 5 AAC 10 AAC Number of starts x 6 Tx 6s F 50 at 40 C 2 30 30 Min operational current 150 mAAC 250 mAAC Rep overload current UL508 TAMB 40 C tON 1s tOFF 9s 50cycles 60 AAC 84 AAC Maximum transient surge current ITSM 325 Ap 600 Ap Maximum off state leakage current 3 mA 3 mA I t 10ms Typical 525 A s 1800 A s Criti...

Page 4: ...t 4kV Performance Criteria 2 Electrical Fast Transient Burst Immunity IEC EN 61000 4 4 Output 2kV Performance Criteria 1 Input 1kV Performance Criteria 1 Electrical Surge Immunity IEC EN 61000 4 5 Output line to line 1kV Performance Criteria 1 Output line to earth 2kV Performance Criteria 1 Input line to line 1kV Performance Criteria 2 Input line to earth 2kV Performance Criteria 2 Radio Interfere...

Page 5: ...housing UL 94 V0 1 L1 Supply connection 2 T1 Load connection A1 positive control signal A2 control ground Environmental Specifications Dimensions Terminal Layout Housing width tolerance 0 5mm 0mm as per DIN43880 All dimensions in mm 5 3 2 17 8 19 5 106 98 90 135 6 35 4 50 6 Connection Diagram Filter Connection diagram In AC controlled types only RG A a varistor is placed across A1 A2 terminals In ...

Page 6: ...WG 1 x 14 12AWG Flexible without end sleeve 2 x 2 5 6 mm2 1 x 2 5 6 mm2 2 x 14 10 AWG 1 x 14 10 AWG Aperture for termination lug 12 3mm CONTROL CONNECTIONS A1 A2 Torque specifications 0 5 Nm 4 4 in lb M3 Pozidriv 1 Use 60 75 C copper Cu conductors Stripping Length X 6mm Rigid Solid Stranded 2 x 0 5 2 5mm2 1 x 0 5 2 5mm2 2 x 18 12 AWG 1 x 18 12 AWG Flexible with end sleeve 2 x 0 5 2 5mm2 1 x 0 5 2 ...

Page 7: ...between enclosure and supply shall not open The door or cover of the enclosure shall not be blown open There shall be no damage to conductors or terminals and the condcutors shall not sepa rate from terminals There shall be no breakage or cracking of insulating bases to the extent that the integrity of the mounting of live parts is impaired Discharge of parts or any risk of fire shall not occur Th...

Reviews: