2-6
Axxius 800 - Release 2.2
Physical Installation
Rack Mounting
To maintain proper convection cooling, maintain at least 1/2 RU between the Axxius
and any other equipment (each Axxius occupies 3 RU of rack space). Therefore, if one
Axxius is mounted above another Axxius, then there would be a total of 1 RU between
them (1/2 RU above the lower unit and 1/2 RU below the upper unit).
Using the 1/2 RU airspace guideline, up to 15 Axxius 800 units may be installed in a
7’ equipment rack.
}
Axxius = 2 RU
Spacing = 1RU
1
2
3
4
5
7
8
9
10
11
12
13
14
15
6
(1/2 above 1/2 below)
1/2 RU free space
1/2 RU free space
1/2 RU free space
1/2 RU free space