2.2 REFRIGERATION SYSTEM DATA
Number of Cylinders
6
Model
06DR
CFM
41
a Compressor/Motor Assembly
Weight (Dry)
118 kg (260 lb)
a. Compressor/Motor Assembly
(CP)
Approved Oil
Castrol Icematic -- SW20
(CP)
Oil Charge
3.6 liters (7.6 U.S. pints)
Oil Sight Glass
The oil level range, with the compressor off,
should be between the bottom and one-eighth
level of the capacity of the sight glass.
b. Expansion Valve Superheat
Verify at --18
_
C
(0
_
F) container box
temperature
4.48 to 6.67
_
C (8 to 12
_
F)
c. Heater Termination Thermostat
Opens
54 (
¦
3)
_
C = 130 (
¦
5)
_
F
c. Heater Termination Thermostat
(HTT)
Closes
38 (
¦
4)
_
C = 100 (
¦
7)
_
F
d High Pressure Switch (HPS)
Cutout
25 (
¦
1.0) kg/cm
@
= 350 (
¦
10) psig
d. High Pressure Switch (HPS)
Cut-In
18 (
¦
0.7) kg/cm
@
= 250 (
¦
10) psig
Charge Requirements -- R-134a
e. Refrigerant Charge
Unit Configuration
2* row
condenser
3* row
condenser
4* row
condenser
e. Refrigerant Charge
Water-Cooled
Condenser
4.5 kg
(9.0 lbs)
4.88 kg
(10.75 lbs)
5.22 kg
(11.5 lbs)
*
Refer to Table 1-1.
NOTE
When replacing components (f.) in section 2.2, refer to the installation instructions included with the
ordered new part for additional information.
Bursts at
35
¦
5% kg/cm
@
= (500
¦
5% psig)
f. Rupture Disc
Torque
(P/N 14-00215-03)
1.4 to 2 mkg (10 to 15 ft-lbs)
f. Rupture Disc
Torque
(P/N 14-00215-04)
6.2 to 6.9 mkg (45 to 50 ft-lbs)
g. Condenser Pressure
Condenser Fan Starts
The condenser fan will start if the condenser
pressure is greater than 14.06 kg/cm
@
(200
psig) OR the condenser fan is OFF for more
than 60 seconds.
g. Condenser Pressure
Transducer (CPT)
Condenser Fan Stops
The condenser fan will stop if the condenser
pressure is less than 9.14 kg/cm
@
(130 psig)
AND the condenser fan remains ON for at least
30 seconds.
h. Unit Weight
Refer to unit model number plate, see Figure 2-1 for location of plate.
i Water Pressure Switch (WP)
Cut-In
0.5
¦
0.2 kg/cm
@
(7
¦
3 psig)
i. Water Pressure Switch (WP)
Cutout
1.6
¦
0.4 kg/cm
@
(22
¦
5 psig)