3-19
T-294-01
INDEFINITELY
, until the user manually enters a
command. Holding the PRE-TRIP key will terminate
the pre-trip mode operation.
When “Auto” or “Auto 1” is allowed to run to
completion without being interrupted, the unit will exit
the pre-trip mode, and return to normal control
operation.
CAUTION
When “Auto 2” is allowed to run to
completion without being interrupted, the
unit will terminate pre-trip and display
“Auto 2” “end.” The unit WILL REMAIN
SUSPENDED in this mode until the user
depresses the ENTER key!
c. Auto
Test
Operation
From
Serial
Communications
Pre-trip may also be initiated via communications. The
operation is the same as for the Auto Test mode
described above except that should a test fail, the
pre-trip mode will automatically terminate. When
initiated via communications, a test may not be
interrupted with an arrow key, but the pre-trip mode can
be terminated with the PRE-TRIP key.
d. Pre-Trip Test Results
At the end of the pre-trip test selection menu, the
message “P,” “rSLts” will be displayed. Pressing the
ENTER key will allow the user to see the results for all
subtests (i.e., 1-0, 1-1, etc). The results will be displayed
as “PASS” or “FAIL” for all the tests run to completion
since power up. If a test has not been run since power up,
“
-- -- -- -- --
” will be displayed.
3.2.2
Pre-Trip Mode
Table 3-5. Pre-Trip Test Codes
Code
No.
TITLE
DESCRIPTION
NOTE
“Auto” or “Auto1” menu includes the following: P, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2’ (Optional)
menu includes the following: P, P1, P2, P3, P4, P5, P6,P7, P8, P9, P10 and rSLts. (Refer to section 3.2.1.)
P
Pre-Trip Initiated
All lights and display segments will be energized for five seconds at the start of
the pre-trip. Since the unit cannot recognize lights and display failures, there are
no test codes or results associated with this phase of pre-trip.
P1-0 Heaters Turned On
S
etup:
Heater must start in the OFF condition, and then be turned on. A current
draw test is done after 15 seconds.
Pass/Fail Criteria:
Passes if change in current draw is within the range
specified.
P1-1 Heaters Turned Off
Setup:
Heater must start in the ON condition, and then be turned off. A current
draw test is done after 10 seconds.
Pass/Fail Criteria:
Passes if change in current draw is within the range
specified.
P2-0 Condenser Fan On
Requirements:
Water pressure switch (WP) input must be closed.
Setup:
Condenser fan is turned ON, a current draw test is done after 15
seconds.
Pass/Fail Criteria:
Passes if change in current draw test is within the range
specified.
P2-1 Condenser Fan Off
Setup:
Condenser fan is turned OFF, a current draw test is done after 10
seconds.
Pass/Fail Criteria:
Passes if change in current draw test is within the range
specified.
P3
Low Speed
Evaporator Fans
R
equirements:
The unit must be equipped with a low speed evaporator fan, as
determined by the Evaporator Fan speed select configuration variable.
NOTE
If the unit is configured for single evaporator fan operation, Pre-Trip tests
P3-0, P3-1, P4-0 and P4-1 will fail immediately if Controller alarm codes
AL11 or AL12 are active at the start of testing.