4-9
T-294-01
which should be active at this point. In arctic mode, the
CCH is energized for 30 minutes to warm the oil in the
compressor, and boil off any liquid refrigerant that may
be present in the crankcase.
If Pre-Trip is initiated during the 30 minute time period,
Pre-Trip will be allowed to run normally. Once Pre-Trip
is over, the controller will revert to its normal control
mode logic.
If ambient is warmer than --10.0
_
C, the system will run
its normal startup logic.
Arctic mode is configurable by using the configuration
variable #29, refer to Table 3-1.
CONTROL TRANSFORMER
= 18 Volt Energized Circuit
= 24 Volt Energized Circuit
= De-energized Circuit
Figure 4-3. Defrost Mode